5
|
4
|
Water quality: daily written records of water quality and test kit kept on site |
No |
No
|
No |
.2535(11) Provide record keeping including daily records of disinfectant residual, pH, drain cover/grate inspections, pool water maintenance, and temperature, if applicable. Provide weekly recordings for cyanuric acid and total alkalinity weekly.
Main drain check was missing from records. Added column to paperwork. |
|
15
|
6
|
Premises: body hook and ring buoy with throw rope or lifeguard with rescue tube provided and properly located |
No |
No
|
No |
.2530(a) Provide ring buoy for rope 1.5 times the width of the pool or 50 ft whichever is less. Rope was longer than 29 feet. Cut during inspection to meet requirement. |
|
16
|
4
|
Premises: fence or barrier with self-closing, self-latching gates properly constructed and maintained |
No |
No
|
No |
.2528(a) Maintain 2" or less under fence and/or gate (post-May 2010). Ground has eroded away under the fence in a few areas creating a gap larger than 2” in some sections. Ground was built up in these areas to reach the 2” requirement. |
|
24
|
4
|
Equipment room: approved pump, filter, and flow meter operating properly |
No |
No
|
No |
.2518(e) Provide a spare basket for pump. There was not spare baskets for either pump. CPO went to pool store and obtained.
.2518(g) Keep flow meter operational. Flow meter for the feature was not operational. It was repaired and read 50gpm. |
|
25
|
2
|
Equipment room: equipment and chemicals kept in a dry, well-ventilated enclosure |
No |
No
|
No |
.2533(e) Provide continuous forced ventilation or cross ventilation in pump room. Vent in pump room appears to be non-functioning. Provide forced ventilation. |