2
|
6
|
Water quality: disinfectant residual provided by |
No |
No
|
No |
Observed chlorine level to be 0.0ppm-0.1ppm. 1.0ppm or more is required. I.S. issued. |
|
3
|
6
|
Water quality: pool water pH |
No |
No
|
No |
Observed pool pH to be 6.8 or less. Safe range is 7.2-7.8. pH must be in the correct range. I.S. issued. |
|
6
|
6
|
Submerged suction outlets meet ASME/ANSI A112.19.8-2007. Single drains protected. (.2537, .2539) GPM= ____Field verification complete=____ |
No |
No
|
No |
Observed vacuum port left open and on. Suction from the vacuum port is a hazard. Never leave it open and uncapped. C. Elmore directed the suction be turned off and the port capped. -CDI. |
|
7
|
4
|
Pool maintenance: pool walls and floor kept clean, free of debris and in good repair |
No |
No
|
No |
Observed some wear on the pool floor. It is not affecting the sanitary condition of the pool at this time. Repair it before it becomes worse. No permit action taken. |
|
11
|
2
|
Pool maintenance: diving equipment, ladders, steps and handrails properly placed, in good repair |
No |
No
|
No |
Observed ladder missing rubber foot. Replace the foot. |
|
15
|
6
|
Premises: body hook and ring buoy with throw rope or lifeguard with rescue tube provided and properly located |
No |
No
|
No |
Observed ring buoy throw rope to be 46ft. 50ft. rope length is required for this pool. The rope was untied and reattached. This provided the correct length. -CDI. |
|
18
|
4
|
Premises: lifeguards present or warning signs posted |
No |
No
|
No |
Observed proper rules sign left in the pump room, not posted on the pool deck. Sign was found and posted. -CDI. |
|
27
|
2
|
Equipment room: filter backwash discharged through an air gap |
No |
No
|
No |
Observed no air gap at the backwash line. |