2
|
6
|
Water quality: disinfectant residual provided by |
No |
No
|
No |
0.5 ppm free chlorine. .2535(4) Maintain chlorine at least 1.0 ppm. - Immediate suspension item. |
|
8
|
4
|
Pool maintenance: surface skimmers (with weirs, baskets and covers) or gutters clean, in good repair, and functioning properly, no floating debris |
No |
No
|
No |
Two of four weirs missing. .2518(k) Replace missing weirs. - Intent to suspend item. |
|
9
|
4
|
Pool maintenance: depth markings and no diving markers or signs visible and properly located |
No |
No
|
No |
Some No Diving markers loose or cracked. .2523(d) No Diving markers shall be written in four inch letters or international 6"x6" no diving in red and black on a white background, and provide a slip resistant walking surface. - Intent to suspend item.
Some Depth markers loose or cracked. .2523(c) Depth markers shall be 4 inches in height and of a contrasting color with the background, clearly visible, and provide a slip resistant walking surface. - Intent to suspend item. |
|
11
|
2
|
Pool maintenance: diving equipment, ladders, steps and handrails properly placed, in good repair |
No |
No
|
No |
One ladder missing the top step. .2521 Install ladders per manufacturer instructions. |
|
16
|
4
|
Premises: fence or barrier with self-closing, self-latching gates properly constructed and maintained |
No |
No
|
No |
Pre-2010 fence < 48" high in places. .2528(a) Pool fence shall be at least 48" in height measured from outside of barrier. |
|
23
|
4
|
Equipment room: chlorine or bromine automatic feeders that meet NSF Standard 50 |
No |
No
|
No |
Automatic feeder not able to feed chlorine. .2535(6) Provide NSF approved automatic chlorinator installed per manufacturer instructions. - Intent to suspend item. |
|
26
|
2
|
Equipment room: valves and pipes identified by color codes or labels |
No |
No
|
No |
Some of the pipe labeling worn or missing. .2518(d) Piping and valves shall be labeled with color codes or labels. |
|
27
|
2
|
Equipment room: filter backwash discharged through an air gap |
No |
No
|
No |
Backwash lines extend into the backwash pit. .2513(b) Filter backwash shall be discharged through an air gap. |
|
29
|
2
|
Dressing and sanitary facilities: required fixtures provided, clean, and in good repair |
No |
No
|
No |
No toilet paper in the men's restroom. .2526(l) Provide toilet paper and dispensers in restrooms. |