5
|
4
|
Water quality: daily written records of water quality and test kit kept on site |
No |
No
|
No |
No recent Cyanuric Acid or Total Alkalinity checks Missing weekend checks for most of the Summer. .2535(11) Provide record keeping including daily records of disinfectant residual, pH, drain cover/grate inspections, and pool water maintenance. Provide weekly recordings for cyanuric acid and total alkalinity. - Intent to suspend item. |
|
9
|
4
|
Pool maintenance: depth markings and no diving markers or signs visible and properly located |
No |
No
|
No |
Depth markers 28 feet apart on pool deck close to pump room. .2523(b) Provide depth markers spaced not to exceed 25 feet when measured along the perimeter of the pool. - Intent to suspend item. |
|
15
|
6
|
Premises: body hook and ring buoy with throw rope or lifeguard with rescue tube provided and properly located |
No |
No
|
No |
Ring buoy without an attached throw rope. .2530(a) Provide USCG approved ring buoy with 50 foot throw rope. - Corrected. |
|
16
|
4
|
Premises: fence or barrier with self-closing, self-latching gates properly constructed and maintained |
No |
No
|
No |
Gate latches less than 54" high. .2528(a) Gate latches shall be 54" in height. - Corrected.
Pre-2010 fence with sections < 48" high, and footholds < 45". .2528(a) Pool fence shall be at least 48" in height measured from outside of barrier with no less than 45" between horizontals. |
|
17
|
4
|
Premises: decks unobstructed, properly drained, free of trip hazards |
No |
No
|
No |
Two skimmer risers missing, 1" below the top of the pavers. .2537(2) Decks shall be kept free of trip hazards or offsets greater than 1/2" due to deterioration or changes from original deck profile. - Intent to suspend item.
One paver to the right of the pool steps missing. .2537(2) Decks shall be kept free of trip hazards or offsets greater than 1/2" due to deterioration or changes from original deck profile. - Intent to suspend item. |
|
24
|
4
|
Equipment room: approved pump, filter, and flow meter operating properly |
No |
No
|
No |
2" flow meter installed on 3" return line. .2518(g) Install flow meter on return line per manufacturer's instructions such that the flow meter reads within 10 percent of true flow .Flow meter be capable of measuring 1.5 times the design flow rate. - Intent to suspend item. |