| Violation Item
| Demerits
| Violation Description
| CDI | R | VR |
|
|
5
|
4
|
Water quality: daily written records of water quality and test kit kept on site |
No |
No
|
No |
Main drain checks missing from few days. Record daily. |
|
6
|
6
|
Submerged suction outlets meet ASME/ANSI A112.19.8-2007. Single drains protected. (.2537, .2539) GPM= ____Field verification complete=____ |
No |
No
|
No |
PDSC form indicates (2) 12MFxxx drain covers. P12xxx drain covers installed. PDSC form indicates incorrect pumps. (1) Pentair Challenger CHII-NI-1.5FE pump and (1) Challenger pump with 2 hp motor. Submit updated PDSC form. 2 hp pump does not work with current equipment in the pump room. Provide true flow of pump per rule requirements if not providing impeller certification. Immediate Suspension issued until paperwork submitted and approved. |
|
7
|
4
|
Pool maintenance: pool walls and floor kept clean, free of debris and in good repair |
No |
No
|
No |
Some damage to pool tile on walls. Keep walls in good repair. |
|
8
|
4
|
Pool maintenance: surface skimmers (with weirs, baskets and covers) or gutters clean, in good repair, and functioning properly, no floating debris |
No |
No
|
No |
3 of 4 skimmers with weirs upside down or out of place. Corrected during inspection.
Water level at 10" below coping. Operating level of a pool should not be more than 9" below deck level so deck can be used as a handhold. .2518 3(d). |
|
12
|
4
|
Pool maintenance: inlets and other fittings in place and in good repair |
No |
No
|
No |
One ladder with ladder rung 6.5" to pool wall. Maintain 3" to 6" from ladder rung to wall. |
|
15
|
6
|
Premises: body hook and ring buoy with throw rope or lifeguard with rescue tube provided and properly located |
No |
No
|
No |
Ring buoy with bore holes and in need of replacement. Replace with USCG approved ring buoy. Immediate Suspension issued. |
|
16
|
4
|
Premises: fence or barrier with self-closing, self-latching gates properly constructed and maintained |
No |
No
|
No |
Main entry gate swings into swimming pool. Gate shall swing away from the swimming pool. Gate latch less than 54" measured from ground. If utilizing gate outside, repair gate to meet code requirements. Main building doors leading to pool deck area - one door not self-closing, self-latching. Door shall self-close. If utilizing building as barrier, door shall self-close, self-latch or self-close with audible alarm. |
|
17
|
4
|
Premises: decks unobstructed, properly drained, free of trip hazards |
No |
No
|
No |
Pots located 5 ft. from pool edge. Maintain 6 ft. clearance around pool.
Deck drain popping up near gate entry. Repair deck drain. |
|
22
|
6
|
Premises: emergency telephone provided |
No |
No
|
No |
Emergency phone not operable. No dial tone and could not verify. Immediate Suspension issued.
.2530(f) Pool telephone shall be capable of directly dialing 911 or another emergency notification system.
.2530(f) Signage with legible letters providing dialing instructions, address of pool and pool telephone number shall be posted at the emergency phone. |
|
23
|
4
|
Equipment room: chlorine or bromine automatic feeders that meet NSF Standard 50 |
No |
No
|
No |
Chlorinator on same power source as pumps. Operator must be able to demonstrate that automated chlorination system detects flow and turns off when no flow. |
|
24
|
4
|
Equipment room: approved pump, filter, and flow meter operating properly |
No |
No
|
No |
Flow meter leaking and does not appear to be installed per manufacturer specifications. Repair leak. Install flow meter per manufacturer instructions. |
|
25
|
2
|
Equipment room: equipment and chemicals kept in a dry, well-ventilated enclosure |
No |
No
|
No |
Pump room floor wet due to leak from flow meter. Keep floor dry.
Pump room left unlocked when not in use. Keep locked when not in use. |
|
30
|
2
|
Dressing and sanitary facilities: approved water source, no cross connections |
No |
No
|
No |
Check valve not approved for fill water. Required ASSE 1013. Installed ASSE1015. If ever replaced, replace with approved check valve for fill line. |
|
33
|
2
|
Dressing and sanitary facilities: hose bibbs and floor drains provided |
No |
No
|
No |
No hose bib in pump room. Provide hose bib or one accessible/operable within 50 ft. of pump room. |