14
|
4
|
Pool maintenance: spa timer working properly |
No |
No
|
No |
.2537(b) Spa times shall not exceed 15 minutes without manual resetting. Spa timer with manual stop screw which prevented timer from exceeding 15 minutes. Turn knob is able to bypass screw allowing spa time in excess of 15 minutes. CDI - larger screw put into place to prevent turning past 15 minutes. |
|
25
|
2
|
Equipment room: equipment and chemicals kept in a dry, well-ventilated enclosure |
No |
No
|
No |
.2534 - Bulk acid not stored in approved chemical storage room. Bulk acid for acid feed system stored outdoors behind the pump/chemical storage area. |