Water quality: daily written records of water quality and test kit kept on site |
No |
No
|
No |
Lifeguard records missing main drain checks, some days and temperature. CPO checks not being made daily for women’s spa.
.2535(11) Provide record keeping including daily records of disinfectant residual, pH, drain cover/grate inspections, pool water maintenance, and temperature, if applicable. Provide weekly recordings for cyanuric acid and total alkalinity weekly.
*Permit item |
|
6
|
6
|
Submerged suction outlets meet ASME/ANSI A112.19.8-2007. Single drains protected. (.2537, .2539) GPM= ____Field verification complete=____ |
No |
No
|
No |
Main drains observed with two rusted screws. 2539(b) All suction fittings shall be installed in accordance with the manufacturer's instructions.
.2539(d) All drain covers shall be kept in good condition. Missing, broken, or cracked fittings shall be replaced or reattached before the pool should be used.
Permit item. Contact Marie Daley at 704-507-6806 when in compliance. Drain covers still secure. Failure to correct by Wednesday 4/6 will result in immediate suspension of permit |
|
24
|
4
|
Equipment room: approved pump, filter, and flow meter operating properly |
No |
No
|
No |
Multiple inlet fittings missing in spa at time of inspection. .2518(i) Arrange inlets to produce uniform circulation. Replace fittings.
*Permit item |
|
25
|
2
|
Equipment room: equipment and chemicals kept in a dry, well-ventilated enclosure |
No |
No
|
No |
Some neutralizer chemicals stored in pump room. .2534(2) Pools constructed after April 1, 2004 shall provide a separate room for chemical storage meeting Rule.2534. |
|
29
|
2
|
Dressing and sanitary facilities: required fixtures provided, clean, and in good repair |
No |
No
|
No |
Hot water in restrooms over 110 degrees F at time of inspection. .2626(i) Water in restrooms shall not exceed 110 F. |