5
|
4
|
Water quality: daily written records of water quality and test kit kept on site |
No |
No
|
No |
Récords kept by guards with incorrect temperature. Records by maintenance missing some main drain checks Temperature at water is right at 104.1 F. Exceeding 104 F is permit suspension, thermometer correct within 1%. Ensure records are accurate. Discussed with CPO and between both log books, information is passable. .2535(11) Provide record keeping including daily records of disinfectant residual, pH, drain cover/grate inspections, pool water maintenance, and temperature, if applicable. Provide weekly recordings for cyanuric acid and total alkalinity weekly. |
|
6
|
6
|
Submerged suction outlets meet ASME/ANSI A112.19.8-2007. Single drains protected. (.2537, .2539) GPM= ____Field verification complete=____ |
No |
No
|
No |
Screws missing from main drains.
.2537(7) Drain covers shall be in good condition and securely attached.
.2539(b) All suction outlets shall be protected by anti-entrapment cover/grates in compliance with APSP-7.
.2539(b) All suction fittings shall be installed in accordance with the manufacturer's instructions.
Operator replaced screws and corrected. |
|
8
|
4
|
Pool maintenance: surface skimmers (with weirs, baskets and covers) or gutters clean, in good repair, and functioning properly, no floating debris |
No |
No
|
No |
Debris in skimmer basket.
.2518(k) Keep skimmers free of debris so skimmers are capable of operating per manufacturer instruction. Operator cleaned and corrected. |
|
23
|
4
|
Equipment room: chlorine or bromine automatic feeders that meet NSF Standard 50 |
No |
No
|
No |
Feeder systems installed are new and have software program on phone which all staff is not currently trained on.
.2535(6) Automatic chlorine and bromine feeder pumps shall be automatically prevented from operating when the circulation pump is not in operation. CPO displayed an “!” When flow was stopped and stated this indicated flow is stopped from feeder. Ensure compliance is met. CPO called regional and discussed. Allowed as acceptable due to knowledge of regional staff, but asked for next inspection to explain on software. |