3
|
6
|
Water quality: pool water pH |
No |
No
|
No |
.2535(1) Maintain pH at 7.2 to 7.8. Observed pH at 6.8. CDI- adjusted to 7.4. |
|
17
|
4
|
Premises: decks unobstructed, properly drained, free of trip hazards |
No |
No
|
No |
.2522(a) Provide 6 ft of clear walking space around the pool at all times. Observed pool furniture within 6 feet of pool. CDI- furniture rearranged. |
|
24
|
4
|
Equipment room: approved pump, filter, and flow meter operating properly |
No |
No
|
No |
.2518(g) Keep flow meter operational. Observed stuck flow meter. |
|
25
|
2
|
Equipment room: equipment and chemicals kept in a dry, well-ventilated enclosure |
No |
No
|
No |
.2533(a) The equipment room door shall have a permanent lock and be kept locked when not in use by the pool operator. Observed pump room door latch not connecting with latching mechanism and therefore was unable to be locked. |