| Violation Item
| Demerits
| Violation Description
| CDI | R | VR |
|
|
5
|
4
|
Water quality: daily written records of water quality and test kit kept on site |
No |
No
|
No |
Cyanuric acid and total alkalinity not recorded weekly. Record weekly. CYA at 60 ppm. Tested during the inspection. Intent to Suspend issued.
DPD-2 reagent expired. Replace reagent. |
|
7
|
4
|
Pool maintenance: pool walls and floor kept clean, free of debris and in good repair |
No |
No
|
No |
Some damage to plaster on pool floor due to acid wash. Continue to monitor and repair if worsens. |
|
11
|
2
|
Pool maintenance: diving equipment, ladders, steps and handrails properly placed, in good repair |
No |
No
|
No |
Step handrail closest to emergency phone loose. Tighten.
Ladder loose. Tighten. |
|
16
|
4
|
Premises: fence or barrier with self-closing, self-latching gates properly constructed and maintained |
No |
No
|
No |
Gate near grill area with part of gate <48" in height. Repair to 48" in height measured from ground. Intent to Suspend issued.
Trash can next to wall provides foothold. Moved during the inspection. |
|
17
|
4
|
Premises: decks unobstructed, properly drained, free of trip hazards |
No |
No
|
No |
Cracked paver near right side grill area and at double door main entry. No offsets >1/2". Does not appear to have sharp edges. Monitor and replace if worsens. |
|
21
|
4
|
Premises: pool and deck lighting provided at pools that operate at night |
No |
No
|
No |
One light not operable in pool. Light blinking. Repair light. Pool is not approved for night swimming. |
|
24
|
4
|
Equipment room: approved pump, filter, and flow meter operating properly |
No |
No
|
No |
Backwash line leaking in pump room. Repair leak. |
|
25
|
2
|
Equipment room: equipment and chemicals kept in a dry, well-ventilated enclosure |
No |
No
|
No |
Floor wet in pump room due to leak at backwash line. Keep pump room floor dry. |
|