Premises: body hook and ring buoy with throw rope or lifeguard with rescue tube provided and properly located |
No |
No
|
No |
Observed two buoys with rope over required length.
.2530(a) Provide ring buoy for rope 1.5 times the width of the pool or 50 ft whichever is less. Operator cut both ropes and corrected to 30' required for pool. . |
|
17
|
4
|
Premises: decks unobstructed, properly drained, free of trip hazards |
No |
No
|
No |
Chairs and furniture within 6' of pool.
.2522(a) Provide 6 ft of clear walking space around the pool at all times. Operator moved chairs and furniture. Corrected. |
|
25
|
2
|
Equipment room: equipment and chemicals kept in a dry, well-ventilated enclosure |
No |
No
|
No |
Items within 3' of piping and equipment in pump room. Some chemicals stored in equipment room. Ventilation in chemical room not pulling at time of inspection.
.2533(c) Valves and controls shall be accessible to the pool operator at all times. Maintain 3 ft. clear walking space in pump room.
.2534(2) Pools constructed after April 1, 2004 shall provide a separate room for chemical storage meeting Rule.2534.
.2534(3) Provide continuous forced ventilation or cross ventilation in chemical storage room. |
|
28
|
2
|
Dressing and sanitary facilities: bathhouse or rest rooms accessible; shower sign posted |
No |
No
|
No |
No signage posted advising showering before entering pool at time of inspection. .2526(a) Post a shower sign visible upon entrance to the pool. |