Submerged suction outlets meet ASME/ANSI A112.19.8-2007. Single drains protected. (.2537, .2539) GPM= ____Field verification complete=____ |
No |
No
|
No |
Flow meter reading 180 gpm at time of inspection. Permit restriction of 150 gpm or less for suction hazard. Operator adjusted skimmer that was plugged and flow decreased to 150 gpm. Corrected.
Send updated PDSC form with new 5% flow meter to pdsc@mecknc.gov |
|
9
|
4
|
Pool maintenance: depth markings and no diving markers or signs visible and properly located |
No |
No
|
No |
One depth marker missing “FT”
.2523(c) Depth markers shall include the word "feet" or symbol "ft". Operator added “FT” and corrected. |
|
11
|
2
|
Pool maintenance: diving equipment, ladders, steps and handrails properly placed, in good repair |
No |
No
|
No |
Ladders greater than 6” from wall. Some ladders loose at time of inspection. .2521(b) Distance between wall and ladder rung shall range 3" to 6" measured from wall.
.2521 Install ladders per manufacturer instructions. |
|
15
|
6
|
Premises: body hook and ring buoy with throw rope or lifeguard with rescue tube provided and properly located |
No |
No
|
No |
Buoy rope too long at time of inspection.
.2530(a) Provide ring buoy for rope 1.5 times the width of the pool or 50 ft whichever is less. Operator cut to 50 ft and corrected. |
|
16
|
4
|
Premises: fence or barrier with self-closing, self-latching gates properly constructed and maintained |
No |
No
|
No |
Front gate not latching at time of inspection.
.2528(a) Gates shall be self-closing, self-latching. Operator adjusted and corrected. |
|
22
|
6
|
Premises: emergency telephone provided |
No |
No
|
No |
Emergency phone missing callback number on signage.
.2530(f) Signage with legible letters providing dialing instructions, address of pool and pool telephone number shall be posted at the emergency phone. Operator added and corrected. |
|
25
|
2
|
Equipment room: equipment and chemicals kept in a dry, well-ventilated enclosure |
No |
No
|
No |
Lights out in chemical room. No 3' clearance around all equipment. Ventilation not working in chemical or pump room. Pool built '85. .2533(e) Provide continuous forced ventilation or cross ventilation in pump room. .2533(c) Valves and controls shall be accessible to the pool operator at all times. Maintain 3 ft. clear walking space in pump room. .2534(3) Provide continuous forced ventilation or cross ventilation in chemical storage room. .2534(6) Provide sufficient lighting in chemical storage room. |
|
33
|
2
|
Dressing and sanitary facilities: hose bibbs and floor drains provided |
No |
No
|
No |
No floor drains in restrooms. .2526(c) Floor drains shall be provided in restrooms. |