5
|
4
|
Water quality: daily written records of water quality and test kit kept on site |
No |
No
|
No |
Records missing daily main drain checks at time of inspection. .2535(11) Provide record keeping including daily records of disinfectant residual, pH, drain cover/grate inspections, pool water maintenance, and temperature, if applicable. Provide weekly recordings for cyanuric acid and total alkalinity weekly. Operator added main drain checks. Corrected. |
|
11
|
2
|
Pool maintenance: diving equipment, ladders, steps and handrails properly placed, in good repair |
No |
No
|
No |
Ladder missing rubber stopper. Ladder greater than 6" from wall.
.2521(b) Distance between wall and ladder rung shall range 3" to 6" measured from wall.
.2521 Install ladders per manufacturer instructions. |
|
13
|
4
|
Pool maintenance: contrasting band on steps and benches |
No |
No
|
No |
Contrasting color band on stair tread over 2”, almost 3” to edge of pool wall. .2521(b) Provide at least 2" contrasting color band to edge of stair treads.
.2521(b) Provide at least 2"x 2" tile for contrasting color band within 1" of adjacent tiles and edge of the stair tread.
*Permit item. Allowing until 2023 to correct due to maintenance required to address and not noted previously when work was completed. |
|
16
|
4
|
Premises: fence or barrier with self-closing, self-latching gates properly constructed and maintained |
No |
No
|
No |
Some gaps in fencing and gate greater than 4" where rods are bent. Pool built '85.
.2528(a) Provide no openings in fence and/or gate greater than 4"x4". Operator bent rods and corrected gate gaps greater than 4". |
|
25
|
2
|
Equipment room: equipment and chemicals kept in a dry, well-ventilated enclosure |
No |
No
|
No |
Lights out in pump and chemical room. Chemicals stored in pump room. Water on floor in equipment room. No 3' clearance around all equipment. Ventilation not working in chemical or pump room. Pool built '85. .2533(e) Provide continuous forced ventilation or cross ventilation in pump room. .2534(2) Pools constructed after April 1, 2004 shall provide a separate room for chemical storage meeting Rule.2534. .2533(b) Provide sufficient lighting in pump room. .2533(c) Valves and controls shall be accessible to the pool operator at all times. Maintain 3 ft. clear walking space in pump room. .2534(3) Provide continuous forced ventilation or cross ventilation in chemical storage room. .2534(6) Provide sufficient lighting in chemical storage room.
.2533(d) Pump room floor shall be kept dry and free of standing water. |
|
27
|
2
|
Equipment room: filter backwash discharged through an air gap |
No |
No
|
No |
No air gap at backwash. .2513(b) Filter backwash shall be discharged through an air gap. |
|
29
|
2
|
Dressing and sanitary facilities: required fixtures provided, clean, and in good repair |
No |
No
|
No |
No toilet paper in restrooms. Provide toilet paper. CPO provided and corrected. |