Premises Information

Return to Inspections
NameBROOKSON FLATS
Address13428 BRYTON GAP BV
 
City/State/ZIP
HUNTERSVILLE NC 28078
Premise Type53 - Year-Round Swimming Pool
CountyMecklenburg
Inspection Date 7/11/2023
Final Score @ Grade
22
General CommentsInspection conducted with CPO Remy Arnao. Pool permitted for night swimming. Unable to verify lights work during the inspection. Will return at dark to verify lights are working. Intent to suspend issued 5) 8)

Violations

 
CDI=Corrected During Inspection  R=Repeat Violation  VR=Verification Required 
Violation Item Demerits Violation Description CDIRVRComments
3 6 Water quality: pool water pH No No No PH 7.9. .2535(1) Maintain pH at 7.2 to 7.8. - Corrected to 7.7.
5 4 Water quality: daily written records of water quality and test kit kept on site No No No Missing some recent records on Sundays. .2535(11) Provide record keeping including daily records of disinfectant residual, pH, drain cover/grate inspections, pool water maintenance, and temperature, if applicable. Provide weekly recordings for cyanuric acid and total alkalinity. - Intent to suspend item.
8 4 Pool maintenance: surface skimmers (with weirs, baskets and covers) or gutters clean, in good repair, and functioning properly, no floating debris No No No Missing 3 of 5 weirs. .2518(k) Provide functional weirs. - Intent to suspend item.
12 4 Pool maintenance: inlets and other fittings in place and in good repair No No No One of the returns plugged with debris. .2537(8) Returns shall be maintained in good working condition and kept in good repair. - Corrected. Debris removed by CPO.
23 4 Equipment room: chlorine or bromine automatic feeders that meet NSF Standard 50 No No No Chlorine > 10ppm. Chlorine feeder keeps adding chlorine even when turned all the way down. .2535(6) Provide NSF approved automatic chlorinator installed per manufacturer instructions. - Operator will manually switch on and off until feeder is recalibrated.