8
|
4
|
Pool maintenance: surface skimmers (with weirs, baskets and covers) or gutters clean, in good repair, and functioning properly, no floating debris |
No |
No
|
No |
.2518(k) Replace missing weirs. Observed 2 of 5 total weirs missing. Replace. |
|
24
|
4
|
Equipment room: approved pump, filter, and flow meter operating properly |
No |
No
|
No |
.2525(b) Heaters shall be equipped with thermostatic controls capable of assuring that the maximum operating temperature of heated public swimming pools other than spas does not exceed 90 degrees Fahrenheit. Such controls shall be accessible only to the operator. Observed heater controls easily accessible to public. Intent to suspend permit issued. |
|
25
|
2
|
Equipment room: equipment and chemicals kept in a dry, well-ventilated enclosure |
No |
No
|
No |
.2533(a) The equipment room door shall have a permanent lock and be kept locked when not in use by the pool operator. Observed pump room unlocked while not in active use. |
|
29
|
2
|
Dressing and sanitary facilities: required fixtures provided, clean, and in good repair |
No |
No
|
No |
.2526(i) Water at shower heads shall not exceed 110 F. Observed water coming out of shower at 116F. |