NameMIDTOWN 205
Address205 S KINGS DR
 
City/State/ZIP
CHARLOTTE NC 28204
Premise Type53 - Year-Round Swimming Pool
CountyMecklenburg
Inspection Date 9/22/2020
Final Score @ Grade
32
General CommentsImmediate Suspension issued for pool pH and ring buoy rope. Once corrected, please contact Katie at 704-309-5494 to schedule a return inspection. Note: Could not verify windows with limiters on to pool deck due to screens in windows. Could not view. Ensure window limiters in place on windows that open up on to pool deck. Limited at 4" or less. Richard Ritch present during inspection. No signature due to covid restrictions.

Violations

 
CDI=Corrected During Inspection  R=Repeat Violation  VR=Verification Required 
Violation Item Demerits Violation Description CDIRVRComments
3 6 Water quality: pool water pH No No No Pool pH >8.4. Maintain at 7.2 to 7.8. Immediate Suspension issued.
5 4 Water quality: daily written records of water quality and test kit kept on site No No No No log books and no test kit reagent for cyanuric acid. Record chlorine, pH and main drain checks daily. Cyanuric acid and total alkalinity weekly. Provide cyanuric acid reagent.
7 4 Pool maintenance: pool walls and floor kept clean, free of debris and in good repair No No No Some algea around main drains. Continue to monitor and rid as needed.
8 4 Pool maintenance: surface skimmers (with weirs, baskets and covers) or gutters clean, in good repair, and functioning properly, no floating debris No No No Water level high. Lower water level so skimmers can function properly.
15 6 Premises: body hook and ring buoy with throw rope or lifeguard with rescue tube provided and properly located No No No Ring buoy rope at 45 ft. Required at 48 ft. Rope appears to have broken. Note - ring buoy may need replacement prior to 2021 operating season. Immediate Suspension issued.
17 4 Premises: decks unobstructed, properly drained, free of trip hazards No No No Some pool furniture 5 ft. to pool edge. Maintain 6 ft clearance around pool in all locations.
23 4 Equipment room: chlorine or bromine automatic feeders that meet NSF Standard 50 No No No Salt being used as primary chlorination. Facility has installed a chlor-king 5S which is rated for 5 lbs per day. Required chlorine production is 5.6 lbs per day. Currently not having issues with chlorine and has a back-up chlorinator to be used in the cooler temperatures. If chlorine is an issue in the future, back-up chlorinator may be required to be used simultaneously with the stick feeder.