6
|
6
|
Submerged suction outlets meet ASME/ANSI A112.19.8-2007. Single drains protected. (.2537, .2539) GPM= ____Field verification complete=____ |
No |
No
|
No |
Catch basins at end of slides murky at time of inspection. Corrected during inspection. Floor visible. |
|
22
|
6
|
Premises: emergency telephone provided |
No |
No
|
No |
Phone not ringing back/operable. Corrected during the inspection. |
|
25
|
2
|
Equipment room: equipment and chemicals kept in a dry, well-ventilated enclosure |
No |
No
|
No |
Pump room and chemicals stored outside. Original construction.
.2533 Pump room/chemical storage room shall be weatherproof with a minimum ceiling height of 7 ft. |
|
29
|
2
|
Dressing and sanitary facilities: required fixtures provided, clean, and in good repair |
No |
No
|
No |
Restroom sinks and toilets with build-up. Keep fixtures clean. Some soap dispensers not operable in women's. Staffing was working on sinks at time of visit to repair. |
|
30
|
2
|
Dressing and sanitary facilities: approved water source, no cross connections |
No |
No
|
No |
Hose bib in family restroom without backflow prevention device. Provide backflow prevention device on all hose bibs. |