7
|
4
|
Pool maintenance: pool walls and floor kept clean, free of debris and in good repair |
No |
No
|
No |
Observed etching on pool floor in multiple areas. Monitor. May require repair in future if worsens. |
|
9
|
4
|
Pool maintenance: depth markings and no diving markers or signs visible and properly located |
No |
No
|
No |
Some depth markers beginning to peel up off pool wall in multiple locations. All depth markers are still clearly visible. Repair/replace once depth marker is not visible. |
|
11
|
2
|
Pool maintenance: diving equipment, ladders, steps and handrails properly placed, in good repair |
No |
No
|
No |
Ladder near slide loose. Tighten ladder. |
|
16
|
4
|
Premises: fence or barrier with self-closing, self-latching gates properly constructed and maintained |
No |
No
|
No |
One door to stairwell not self-latching. Repaired during the inspection to self-latch. |
|
17
|
4
|
Premises: decks unobstructed, properly drained, free of trip hazards |
No |
No
|
No |
Floats located next to lazy river entry with less than 5 ft. from float to wall. Maintain 5 ft. clearance around the pool in all locations. |
|
22
|
6
|
Premises: emergency telephone provided |
No |
No
|
No |
Emergency phone located in the guard room. Sign was removed. Additional signage added during the inspection to indicate location of emergency phone. Temporary signage added. Provide permanent signage visible from all areas of the pool deck for the location of the emergency phone. |
|
29
|
2
|
Dressing and sanitary facilities: required fixtures provided, clean, and in good repair |
No |
No
|
No |
Hot water in women's restroom at 113.3 F. Maintain at 110 F or below.
Leak at cold water handle at sink furthest from pool. Repair sink.
Men's locker room not viewed at time of inspection. Could not access. |