Select your filters and click the Search button to search for data, or click Clear to clear all filters
 
Logo Main Menu
Mecklenburg County Health Dept
Public Health Inspections
Select your filters and click the Search button to search for data, or click Clear to clear all filters
 
  
 

Premises Information

Return to Inspections
NameAPARTMENTS AT HOLLY CREST - INDOOR SPA
Address16312 HOLLY CREST LN
 
City/State/ZIP
HUNTERSVILLE NC 28078
Premise Type55 - Year-Round Spa
CountyMecklenburg
Inspection Date 7/21/2025
Final Score @ Grade
20
General CommentsInspection conducted with CPO Ricardo Trujillo. Ricardo is the new CPO. Updated our files. New management company. Emailed manager a copy of the application. Will need to update and return it to our office so we can update our files. Verified feature pump flow at 90 GPM. Max allowed is 119 GPM. Spa switched from using automatic chlorine system to bromine erosion feeder. Static on Kings III emergency phone. Recommend having phone and line checked/repaired. *Note* Inspection re-entered to correct status. Lost signature for CPO. Intent to suspend issued 5) 8) 12)

Violations

 
CDI=Corrected During Inspection  R=Repeat Violation  VR=Verification Required 
Violation Item Demerits Violation Description CDIRVRComments
4 6 Water quality: water temperature of heated pool No No No Observed water temperature at 105.0F. .2535(12) Heated spa temperature greater than 104 F. Maintain spa temperature at 104F or below. - New management staff not sure where water heater is to adjust. Will follow up with facility to ensure temperature is corrected.
5 4 Water quality: daily written records of water quality and test kit kept on site No No No No records since 7/15. No place on sheet for main drain checks. .2535(11) Provide record keeping including daily records of disinfectant residual, pH, drain cover/grate inspections, pool water maintenance, and temperature, if applicable. Provide weekly recordings for cyanuric acid and total alkalinity. - Intent to suspend item.
8 4 Pool maintenance: surface skimmers (with weirs, baskets and covers) or gutters clean, in good repair, and functioning properly, no floating debris No No No Water 3-4 inches below the gutter. .2518(k) Water level shall be maintained above the level of the overflow trough on gutter. - Intent to suspend item.
12 4 Pool maintenance: inlets and other fittings in place and in good repair No No No One spa jet fitting missing. .2537(8) Fittings and/or face plates shall be replaced when damaged and kept in good repair. - Intent to suspend item.
25 2 Equipment room: equipment and chemicals kept in a dry, well-ventilated enclosure No No No Fan not observed in pump room. .2533(e) Provide continuous forced ventilation or cross ventilation in pump room. Leak at pump. .2533(d) Pump room floor shall be kept dry and free of standing water. Chemicals stored in the pump room. .2534(2) Pools constructed after April 1, 2004 shall provide a separate room for chemical storage meeting Rule.2534. Items stored by spa piping. .2533(c) Valves and controls shall be accessible to the pool operator at all times. Maintain 3 ft. clear walking space in pump room.