3
|
6
|
Water quality: pool water pH |
No |
No
|
No |
.2535(1) Maintain pH at 7.2 to 7.8. Pool water pH 8.0. Corrected to 7.4 during inspection. |
|
16
|
4
|
Premises: fence or barrier with self-closing, self-latching gates properly constructed and maintained |
No |
No
|
No |
Brick wall and other parts of fencing creating horizontals (handholds/footholds) less than 45" in height. Gaps under fencing greater than 4" in some areas on hill. Maintain horizontals no less than 45" in height. Pool built '92, no permit action. Ensure windows onto pool deck do not open greater than 4" (unable to verify).
.2528(b) Maintain no greater than 4" under fence and/or gate (pre-May 2010).
Door to clubhouse leads directly onto pool deck and cannot be propped open. Remove door stop to as door should never be propped open. |
|
22
|
6
|
Premises: emergency telephone provided |
No |
No
|
No |
.2530(f) Emergency phone shall remain operable. Emergency call box not operating as designed/intended. Box dials 911, however, operator unable to clearly hear communication. EHS attempted to call two times - first time 911 disconnected as they could not hear. The second call EHS yelled directly into box and operator confirmed barely able to hear but did confirm location information. Similar issue was noted with previous inspection in September of 2022. Should there be an actual emergency, 911 operations would likely not be able to communicate.
30 day intent to suspend the permit issued. |
|
25
|
2
|
Equipment room: equipment and chemicals kept in a dry, well-ventilated enclosure |
No |
No
|
No |
Chemicals stored in pump room. Items within 3' of piping. Pool built '92.
.2533(c) Valves and controls shall be accessible to the pool operator at all times. Maintain 3 ft. clear walking space in pump room.
.2534(2) Pools constructed after April 1, 2004 shall provide a separate room for chemical storage meeting Rule.2534. |
|
26
|
2
|
Equipment room: valves and pipes identified by color codes or labels |
No |
No
|
No |
Labels fading piping .2518(d) Piping and valves shall be labeled with color codes or labels. |
|
27
|
2
|
Equipment room: filter backwash discharged through an air gap |
No |
No
|
No |
No air gap at backwash. Pool built 1992. .2513(b) Filter backwash shall be discharged through an air gap |
|
33
|
2
|
Dressing and sanitary facilities: hose bibbs and floor drains provided |
No |
No
|
No |
No floor drains in restroom. No hose bib in restroom within 50’ Pool built ‘92. .2526(c) Floor drains shall be provided in restrooms.
.2526(d) Provide hose bib so that all parts of restroom can be reached with a 50 ft hose. |