Select your filters and click the Search button to search for data, or click Clear to clear all filters
 
Logo Main Menu
Mecklenburg County Health Dept
Public Health Inspections
Select your filters and click the Search button to search for data, or click Clear to clear all filters
 
  
 

Premises Information

Return to Inspections
NameHOME 2 SUITES
Address625 MCCULLOUGH DR
 
City/State/ZIP
CHARLOTTE NC 28262
Premise Type53 - Year-Round Swimming Pool
CountyMecklenburg
Inspection Date 12/17/2019
Final Score @ Grade
26
General CommentsNew Eco Lab cal hypo automatic feeder installed. Ensure that chemical feeder was installed correctly and any applicable plumbing/electrical permits were pulled. Escutcheon plate missing on handrail. Recommend installing a new escutcheon plate to prevent injury or tampering with the screw for the handrail anchor. Pump, bonding wires, and other equipment heavily rusted from leaks in the pump room. Maintain everything in good operating condition. Intent to suspend issued. 5) 8) 16)

Violations

 
CDI=Corrected During Inspection  R=Repeat Violation  VR=Verification Required 
Violation Item Demerits Violation Description CDIRVRComments
5 4 Water quality: daily written records of water quality and test kit kept on site No No No No records kept on CPO's off days. Missing daily main drain and temperature checks. .2535(11) Provide record keeping including daily records of disinfectant residual, pH, drain cover/grate inspections, pool water maintenance, and temperature. Provide weekly recordings for total alkalinity and cyanuric acid if used. - Intent to suspend item.
8 4 Pool maintenance: surface skimmers (with weirs, baskets and covers) or gutters clean, in good repair, and functioning properly, no floating debris No No No Both weirs missing. .2518(k) Replace missing weirs. - Intent to suspend item.
15 6 Premises: body hook and ring buoy with throw rope or lifeguard with rescue tube provided and properly located No No No Throw rope for one of the ring buoys 5 feet too short. .2530(a) Provide 22 foot throw rope for U. S. Coast Guard approved ring buoy. - Corrected.
16 4 Premises: fence or barrier with self-closing, self-latching gates properly constructed and maintained No No No Door to patio area sticks, not self-latching. .2537(b) All gates and doors shall be self-closing, self-latching. - Intent to suspend item.
24 4 Equipment room: approved pump, filter, and flow meter operating properly No No No Flow meter stuck. .2518(g) Keep flow meter operational. - Corrected by operator.
25 2 Equipment room: equipment and chemicals kept in a dry, well-ventilated enclosure No No No Leak in the pump room. .2533(d) Pump room floor shall be kept dry and free of standing water. Acid tub stored in the pump room for newly installed Eco Lab chemical feeder. Store all chemicals in the chemical storage room.
29 2 Dressing and sanitary facilities: required fixtures provided, clean, and in good repair No No No Hot water in restroom 112.5F. .2526(i) Water in restrooms shall not exceed 110 F.