5
|
4
|
Water quality: daily written records of water quality and test kit kept on site |
No |
No
|
No |
pH indicator out of reagent. Provide pH indicator reagent to test pH. Intent to Suspend issued. |
|
6
|
6
|
Submerged suction outlets meet ASME/ANSI A112.19.8-2007. Single drains protected. (.2537, .2539) GPM= ____Field verification complete=____ |
No |
No
|
No |
PDSC form not filled out completely and incorrect information for location of main drains for feature. Operator filled out new PDSC during inspection. |
|
7
|
4
|
Pool maintenance: pool walls and floor kept clean, free of debris and in good repair |
No |
No
|
No |
Some algae on pool walls and on drain covers. Keep walls clean and in good repair. Continue to monitor algae and treat as required. |
|
9
|
4
|
Pool maintenance: depth markings and no diving markers or signs visible and properly located |
No |
No
|
No |
1 ft. depth marker blocked by pool furniture near restroom entrance. Furniture moved during the inspection. |
|
16
|
4
|
Premises: fence or barrier with self-closing, self-latching gates properly constructed and maintained |
No |
No
|
No |
Multiple windows opening on to pool deck without limiters. All windows that open directly on to the pool deck shall have window limiters, opening no greater than 4". Intent to Suspend issued. |
|
17
|
4
|
Premises: decks unobstructed, properly drained, free of trip hazards |
No |
No
|
No |
Pavers used as decking around pool. Sealed with polymeric sand. Sand has washed out in multiple locations. Re-seal prior to 2022 operating permit. Pavers shall be sealed with polymeric sand to ensure impervious surface within 6 ft. of pool. |
|
22
|
6
|
Premises: emergency telephone provided |
No |
No
|
No |
Phone connection bad with 911 on initial call. Operator spoke to Kings III during the inspection who reset the line. 911 and EHS clearly audible after reset. |
|
23
|
4
|
Equipment room: chlorine or bromine automatic feeders that meet NSF Standard 50 |
No |
No
|
No |
Chlorinator/automated pH not calibrated. Reading 8.4 when pH at 7.4. Calibrate chlorinator/feeder. Intent to Suspend issued. |
|
25
|
2
|
Equipment room: equipment and chemicals kept in a dry, well-ventilated enclosure |
No |
No
|
No |
Floor wet in pump room after backwash. Backwash pit tied to floor drain and water backs up on to pump room floor when backwashed. Repair drainage. Ensure flooring kept dry. |