8
|
4
|
Pool maintenance: surface skimmers (with weirs, baskets and covers) or gutters clean, in good repair, and functioning properly, no floating debris |
No |
No
|
No |
.2518(k) Keep skimmers free of debris so skimmers are capable of operating per manufacturer instruction. Five of nine skimmers full of debris. Cleaning needed. |
|
23
|
4
|
Equipment room: chlorine or bromine automatic feeders that meet NSF Standard 50 |
No |
No
|
No |
.2535(6) Automatic chlorine and bromine feeder pumps shall be automatically prevented from operating when the circulation pump is not in operation. .2535 Automatic acid feeder shall be automatically prevented from operating when the circulation pump is not in operation. Initial attempt to check power shut off to pump resulted in feeders continuing to operate. CDI- CPO was able to repair, and second attempt was successful. Power was shut off to pump, feeders did stop as required and resumed timely when power turned back on. |