Select your filters and click the Search button to search for data, or click Clear to clear all filters
 
Logo Main Menu
Mecklenburg County Health Dept
Public Health Inspections
Select your filters and click the Search button to search for data, or click Clear to clear all filters
 
  
 

Premises Information

Return to Inspections
NameHOLIDAY INN EXPRESS & SUITES CHARLOTTE AIRPORT
Address108 AIRPORT COMMONS DR
 
City/State/ZIP
CHARLOTTE NC 28208
Premise Type53 - Year-Round Swimming Pool
CountyMecklenburg
Inspection Date 9/16/2024
Final Score @ Grade
16
General CommentsPerformed inspection with CPO Jefferson Pinos. Intent to suspend issued for damaged skimmer basket and missing weir. Call or text EHS Devon Moeller when repaired. 7049981122

Violations

 
CDI=Corrected During Inspection  R=Repeat Violation  VR=Verification Required 
Violation Item Demerits Violation Description CDIRVRComments
2 6 Water quality: disinfectant residual provided by No No No .2535(4) Maintain chlorine at least 1.0 ppm. Chlorine testing at 0ppm. Operator corrected to 1.0ppm. No permit action.
5 4 Water quality: daily written records of water quality and test kit kept on site No No No .2535(11) Provide record keeping including daily records of disinfectant residual, pH, drain cover/grate inspections, pool water maintenance, and temperature, if applicable. Provide weekly recordings for cyanuric acid and total alkalinity weekly. Some weekly readings for CA and TA missing. Ensure CA and TA are recorded weekly. No permit action.
8 4 Pool maintenance: surface skimmers (with weirs, baskets and covers) or gutters clean, in good repair, and functioning properly, no floating debris No No No .2518(k) Replace missing weirs. .2518(k) Replace missing or damaged skimmer basket. Missing weir and broken skimmer basket in skimmer by door. Intent to suspend item.
25 2 Equipment room: equipment and chemicals kept in a dry, well-ventilated enclosure No No No .2533(d) Pump room floor shall be kept dry and free of standing water. Observed water on pump room floor coming from leak at chlorinator and filter. .2534(2) Pools constructed after April 1, 2004 shall provide a separate room for chemical storage meeting Rule.2534. Some chemicals stored in pump room. Move chemicals to designated chemical storage room