Select your filters and click the Search button to search for data, or click Clear to clear all filters
 
Logo Main Menu
Mecklenburg County Health Dept
Public Health Inspections
Select your filters and click the Search button to search for data, or click Clear to clear all filters
 
  
 

Premises Information

Return to Inspections
NameHOLIDAY INN EXPRESS & SUITES CHARLOTTE AIRPORT
Address108 AIRPORT COMMONS DR
 
City/State/ZIP
CHARLOTTE NC 28208
Premise Type53 - Year-Round Swimming Pool
CountyMecklenburg
Inspection Date 3/30/2017
Final Score @ Grade
30
General Comments

Violations

 
CDI=Corrected During Inspection  R=Repeat Violation  VR=Verification Required 
Violation Item Demerits Violation Description CDIRVRComments
3 6 Water quality: pool water pH No No No pH > 8.4. Maintain between 7.2 and 7.8. - Immediate suspension item.
5 4 Water quality: daily written records of water quality and test kit kept on site No No No No total alkalinity or cyanuric acid records. Back up chlorinator using stabilzed chlorine. Check at least weekly total alkalinity and cyanuric acid. - Intent to suspend item. Missing some days. Looks like pool is not checked on CPO's day off. Check daily Cl, pH, main drains, temperature and at least weekly total alkalinity and cyanuric acid - Intent to suspend item.
8 4 Pool maintenance: surface skimmers (with weirs, baskets and covers) or gutters clean, in good repair, and functioning properly, no floating debris No No No Far skimmer initially with no flow. After backwashing far skimmer still had inadequate flow. Provide functional skimmers. - Intent to suspend item.
15 6 Premises: body hook and ring buoy with throw rope or lifeguard with rescue tube provided and properly located No No No Ring buoy with loose beckets. Replace with US Coast Guard approved ring buoy and 24 foot throw rope. - Immediate suspension item.
22 6 Premises: emergency telephone provided No No No Incorrect dialing instructions for emergency phone. Instructions state that user must dial 911 to reach 911. Only need to lift the receiver to reach 911. Change emergency phone signage to accurate reflect what must be done to reach 911. - Immediate suspension item.
24 4 Equipment room: approved pump, filter, and flow meter operating properly No No No Flow meter reading < 20 gpm, filter pressure guage reading 30 psi. Backwash regularly to maintain filter and proper turnover. After short backwash filter pressure guage and flow meter read closer to normal readings.