Premises: body hook and ring buoy with throw rope or lifeguard with rescue tube provided and properly located |
No |
No
|
No |
.2530(a) Provide ring buoy for rope 1.5 times the width of the pool or 50 ft whichever is less. Observed buoy rope to be in excess of 1.5 times the width of the pool. CDI - Buoy rope was shortened to the required 24ft length. |
|
16
|
4
|
Premises: fence or barrier with self-closing, self-latching gates properly constructed and maintained |
No |
No
|
No |
.2528(a) Access gates shall swing away from the pool and be self-latching, self-closing unless an attendant AND lifeguard are present. Observed two access gates to pool deck not self latching. CDI - Pool operator was able to repair self latching locks during inspection.
.2528(a) Ground level doors shall be self-closing, self-latching or child protected by audible alarm. Observed ground level door to pool deck not self latching and without audible alarm. Pool operator stated that pool door is left unlocked and unlatched during apartment building office hours. CDI - Pool Operator was able to repair door so that it is now self latching. Pool operator was informed that door shall remain self latching at all times or use an audible alarm. |
|
22
|
6
|
Premises: emergency telephone provided |
No |
No
|
No |
.2530(f) Emergency phone shall remain operable. Emergency call box was not operating a start of inspection. CDI - Pool operator placed call to Kings III customer service and was told to contact phone company. Phone company was able to restore service during inspection. Kings III call box was able to contact emergency services. |