3
|
6
|
Water quality: pool water pH |
No |
No
|
No |
pH 8.1. .2535(1) Maintain pH at 7.2 to 7.8. - Pre-permit item. |
|
6
|
6
|
Submerged suction outlets meet ASME/ANSI A112.19.8-2007. Single drains protected. (.2537, .2539) GPM= ____Field verification complete=____ |
No |
No
|
No |
PDSC form does not match what was installed. Observed VGB 2017 Aquastar 1216xxx drain covers installed on pool wall for feature pump. .2539(c) All pools, prior to permit issuance, shall provide documentation to the Department to verify suction outlet safety compliance. - Pre-permit item.
Observed pop-up covers on skimmer equalizer lines. Lines plastered over on pool wall. Must be abandoned per state guidelines per PDSC form. .2539(c) All pools, prior to permit issuance, shall provide documentation to the Department to verify suction outlet safety compliance. - Pre-permit item. |
|
11
|
2
|
Pool maintenance: diving equipment, ladders, steps and handrails properly placed, in good repair |
No |
No
|
No |
Ladders loose. .2521 Install ladders per manufacturer instructions. |
|
12
|
4
|
Pool maintenance: inlets and other fittings in place and in good repair |
No |
No
|
No |
Eyeball fitting missing on auto-fill line. .2537(8) Fittings and/or face plates shall be replaced when damaged and kept in good repair. - Pre-permit item.
Overflow grate broken. .2537(8) Fittings and/or face plates shall be replaced when damaged and kept in good repair. - Pre-permit item. |
|
21
|
4
|
Premises: pool and deck lighting provided at pools that operate at night |
No |
No
|
No |
One underwater light not fully installed. Other light with crooked retaining screw. .2524(c) Install lighting fixtures per manufacturers instructions such that they do not present a hazard to the public. - Pre-permit item. |
|
22
|
6
|
Premises: emergency telephone provided |
No |
No
|
No |
Not able to hear Kings III operator. .2530(f) Emergency phone shall remain operable. - Pre-permit item. |
|
24
|
4
|
Equipment room: approved pump, filter, and flow meter operating properly |
No |
No
|
No |
.2518(g) Install flow meter on return line per manufacturer instructions such that it reads with +/- 10% of true flow. - Pre-permit item. |