2
|
6
|
Water quality: disinfectant residual provided by |
No |
No
|
No |
0.3 ppm free chlorine. .2535(4) Maintain chlorine at least 1.0 ppm. - Pre-permit item. |
|
5
|
4
|
Water quality: daily written records of water quality and test kit kept on site |
No |
No
|
No |
Spotty records. One reading for the month of July. .2535(11) Provide record keeping including daily records of disinfectant residual, pH, drain cover/grate inspections, pool water maintenance, and temperature, if applicable. Provide weekly recordings for cyanuric acid and total alkalinity. - Pre-permit item.
CPO on record no longer works here. Provide CPO documentation for new CPO. .2537(c) Pool owner shall provide for the operation and maintenance of the pool by a trained pool operator. - Pre-permit item. |
|
8
|
4
|
Pool maintenance: surface skimmers (with weirs, baskets and covers) or gutters clean, in good repair, and functioning properly, no floating debris |
No |
No
|
No |
Skimmers turned off in the pump room. .2518(k) Skimmers shall be operable. - Corrected.
Weir not installed. .2518(k) Provide functional weirs. - Pre-permit item. |
|
16
|
4
|
Premises: fence or barrier with self-closing, self-latching gates properly constructed and maintained |
No |
No
|
No |
Fence < 48” high in places, mostly due to pine straw that was added. .2528(a) Pool fence shall be at least 48" in height measured from outside of barrier. - Pre-permit item. |
|
23
|
4
|
Equipment room: chlorine or bromine automatic feeders that meet NSF Standard 50 |
No |
No
|
No |
Automatic chlorinator plugged in directly, pressure/flow switch bypassed. .2535 Automatic acid feeder shall be automatically prevented from operating when the circulation pump is not in operation. - Pre-permit item. |
|
24
|
4
|
Equipment room: approved pump, filter, and flow meter operating properly |
No |
No
|
No |
Fencing around heater < 48” high in places. .2525(b) Heaters shall be equipped with thermostatic controls capable of assuring that the maximum operating temperature of heated public swimming pools other than spas does not exceed 90 degrees Fahrenheit. Such controls shall be accessible only to the operator. - Pre-permit item. |
|
25
|
2
|
Equipment room: equipment and chemicals kept in a dry, well-ventilated enclosure |
No |
No
|
No |
Items stored by equipment. .2533(c) Valves and controls shall be accessible to the pool operator at all times. Maintain 3 ft. clear walking space in pump room. |