| Violation Item
| Demerits
| Violation Description
| CDI | R | VR |
|
|
5
|
4
|
Water quality: daily written records of water quality and test kit kept on site |
No |
No
|
No |
Some days missing from logs. Chlorine and pH at same value for past month. No cyanuric acid or alkalinity testing recorded. Keep daily logs. Assure cyanuric acid and alkalinity are tested and recorded weekly. Record chlorine, pH and main drain checks daily. Intent to Suspend issued.
Test kit with chlorine cylinder beginning to turn black. Replace test kit. Intent to Suspend issued. |
|
6
|
6
|
Submerged suction outlets meet ASME/ANSI A112.19.8-2007. Single drains protected. (.2537, .2539) GPM= ____Field verification complete=____ |
No |
No
|
No |
PDSC form with incorrect main drain covers. No suction hazard. Required updated form within 1 week or permit will be suspended. |
|
8
|
4
|
Pool maintenance: surface skimmers (with weirs, baskets and covers) or gutters clean, in good repair, and functioning properly, no floating debris |
No |
No
|
No |
One weir missing skimmer and one damaged skimmer basket. Replace weir and basket. Intent to Suspend issued. |
|
11
|
2
|
Pool maintenance: diving equipment, ladders, steps and handrails properly placed, in good repair |
No |
No
|
No |
Observed multiple ladders >6" from pool wall from ladder rung to wall. Maintain 3" to 6" between ladder rung and wall.
One ladder missing end cap. Replace end cap.
>10 ft between ladders at step entry.
Pool built 1/1/1985. |
|
15
|
6
|
Premises: body hook and ring buoy with throw rope or lifeguard with rescue tube provided and properly located |
No |
No
|
No |
Ring buoy rope less than 42 ft. Corrected at time of inspection.
General Comment - Replace USCG approved ring buoy within 30 days. Current buoy is starting to degrade from sunlight. Grab rope is brittle but still intact. |
|
16
|
4
|
Premises: fence or barrier with self-closing, self-latching gates properly constructed and maintained |
No |
No
|
No |
Door from restrooms not self-closing, self-latching when restroom hallway door is closed. All doors on to pool deck shall be self-closing, self-latching. Intent to Suspend issued.
3 of 4 gates were locked. Gates shall self-close, self-latch. Intent to Suspend issued.
One gate not closing and does not self-close, self-latch. Operator indicated that all gates except for one were NOT used by the public. If property does not intend to utilize gates and not required by Code Enforcement, gates shall be made to no longer be a gate in order to meet rule of .2528. Intent to Suspend issued.
One gate handle <40" measured from ground to handle. Eliminate foothold. Intent to Suspend issued.
Fence <48" in height in some locations. Pool built prior to 2010. |
|
17
|
4
|
Premises: decks unobstructed, properly drained, free of trip hazards |
No |
No
|
No |
Damage to deck drain with protrusion greater than 1/2" and some damage to deck at same location. Eliminate offsets greater than 1/2". Intent to Suspend issued.
Some damage to coping near steps. No offsets >1/2". Continue to monitor. |
|
23
|
4
|
Equipment room: chlorine or bromine automatic feeders that meet NSF Standard 50 |
No |
No
|
No |
Facility is utilizing salt as primary chlorination. Not approved for salt as primary. Provide spec sheets for salt generator. Intent to Suspend issued. |
|
27
|
2
|
Equipment room: filter backwash discharged through an air gap |
No |
No
|
No |
No air gap at backwash line to pit. Pool built 1/1/1985. Provide air gap at backwash line to pit. |
|
30
|
2
|
Dressing and sanitary facilities: approved water source, no cross connections |
No |
No
|
No |
No check valve at water line hook up to fill line.
.2512(b) Water introduced into the pool, either directly or by the circulation system, shall be supplied through an air gap, anti-siphon vacuum breaker, or backflow preventer. |
|
33
|
2
|
Dressing and sanitary facilities: hose bibbs and floor drains provided |
No |
No
|
No |
No hose bib in pool equipment room or restrooms. Provide hose bib with backflow prevention in restrooms and pump room. |