5
|
4
|
Water quality: daily written records of water quality and test kit kept on site |
No |
No
|
No |
No cyanuric acid checks. .2535(11) Provide record keeping including daily records of disinfectant residual, pH, drain cover/grate inspections, pool water maintenance, and temperature, if applicable. Provide weekly recordings for cyanuric acid and total alkalinity. - Intent to suspend item. |
|
8
|
4
|
Pool maintenance: surface skimmers (with weirs, baskets and covers) or gutters clean, in good repair, and functioning properly, no floating debris |
No |
No
|
No |
Observed one weir missing. .2518(k) Install functional weirs. |
|
15
|
6
|
Premises: body hook and ring buoy with throw rope or lifeguard with rescue tube provided and properly located |
No |
No
|
No |
Throw rope for ring buoy heavily knotted. .2530(a) Provide US Coast Guard approved ring buoy with attached 50 foot throw rope at least 1/4 inch in diameter. - Corrected. |
|
16
|
4
|
Premises: fence or barrier with self-closing, self-latching gates properly constructed and maintained |
No |
No
|
No |
Fencing less than 48” high in places, mostly due to pine straw. .2528(a) Pool fence shall be at least 48" in height measured from outside of barrier. - Intent to suspend item. |
|
23
|
4
|
Equipment room: chlorine or bromine automatic feeders that meet NSF Standard 50 |
No |
No
|
No |
Erosion chlorinator does not appear to be installed according to manufacturer’s instructions. .2535(6) Provide NSF approved automatic chlorinator installed per manufacturer instructions. - Intent to suspend item. |
|
24
|
4
|
Equipment room: approved pump, filter, and flow meter operating properly |
No |
No
|
No |
Fencing around heater < 48” high in places. .2525(b) Heaters shall be equipped with thermostatic controls capable of assuring that the maximum operating temperature of heated public swimming pools other than spas does not exceed 90 degrees Fahrenheit. Such controls shall be accessible only to the operator. - Intent to suspend item. |
|
25
|
2
|
Equipment room: equipment and chemicals kept in a dry, well-ventilated enclosure |
No |
No
|
No |
Leak in the pump room. .2533(d) Pump room floor shall be kept dry and free of standing water.
Lights not working in pump room. .2533(b) Provide sufficient lighting in pump room.
Lights not working in chemical storage room. .2534(6) Provide sufficient lighting in chemical storage room.
Fan not working in chemical storage room. .2534(3) Provide continuous forced ventilation or cross ventilation in chemical storage room. |
|
26
|
2
|
Equipment room: valves and pipes identified by color codes or labels |
No |
No
|
No |
Some piping not labeled. .2518(d) Piping and valves shall be labeled with color codes or labels. |
|
27
|
2
|
Equipment room: filter backwash discharged through an air gap |
No |
No
|
No |
No air gap for backwash. .2513(b) Filter backwash shall be discharged through an air gap. |