Submerged suction outlets meet ASME/ANSI A112.19.8-2007. Single drains protected. (.2537, .2539) GPM= ____Field verification complete=____ |
No |
No
|
No |
PDSC form does not match what is on file. Observed VGB 2008 Aquastar A10CFR covers installed. PDSC form states VGB 2017 A10RCFR covers installed. .2539(c) All pools, prior to permit issuance, shall provide documentation to the Department to verify suction outlet safety compliance. - Pre-permit item. |
|
9
|
4
|
Pool maintenance: depth markings and no diving markers or signs visible and properly located |
No |
No
|
No |
Three depth markers on pool wall on the sun shelf missing. Says 0FT instead of 0FT 6Inches. .2523(b) Provide accurate depth markers spaced not to exceed 25 feet when measured along the perimeter of the pool. - Pre-permit item. |
|
16
|
4
|
Premises: fence or barrier with self-closing, self-latching gates properly constructed and maintained |
No |
No
|
No |
Magna-latches < 54” high. 2528(a) Gate latches shall be 54" in height. - Pre-permit item. |
|
24
|
4
|
Equipment room: approved pump, filter, and flow meter operating properly |
No |
No
|
No |
Flow meter stuck. .2518(g) Keep flow meter operational. - Corrected.
Pool replastered 2 weeks ago. Eyeball fitting installed on vacuum line by sun shelf. .2518(f) Provide a vacuum cap or self-closing cap for pools built after May 1, 2010. - Pre-permit item. |
|
25
|
2
|
Equipment room: equipment and chemicals kept in a dry, well-ventilated enclosure |
No |
No
|
No |
Leak in the pump room. .2533(d) Pump room floor shall be kept dry and free of standing water. |
|
28
|
2
|
Dressing and sanitary facilities: bathhouse or rest rooms accessible; shower sign posted |
No |
No
|
No |
Shower still winterized. .2526(h) Shower(s) shall be provided. |