Premises: body hook and ring buoy with throw rope or lifeguard with rescue tube provided and properly located |
No |
No
|
No |
Ring buoy rope in disrepair - torn apart and tied together. Replaced with 50 ft rope at time of inspection. .2530(a) Provide ring buoy for rope 1.5 times the width of the pool or 50 ft whichever is less.
Grab rope on USCG approved ring buoy beginning to degrade due to weather. Still intact. Replace within 1 week. .2530(a) Provide USCG approved ring buoy. A rescue tube with lifeguard may be substituted for ring buoy. |
|
16
|
4
|
Premises: fence or barrier with self-closing, self-latching gates properly constructed and maintained |
No |
No
|
No |
New magna-latch gate latches installed at 52" measured from ground. .2528(a) Gate latches shall be 54" in height measured from ground to top of latch. Intent to Suspend issued.
Openings in fencing >2" where old hardware was removed for door handles. .2528(b) Decorative cut-outs on fence and/or gate shall not exceed 1.75 inches. Intent to Suspend issued.
Heater outside of pool fence providing foothold. Eliminate foothold. .2528(b) Horizontals shall not be located less than 45" in height. |
|
22
|
6
|
Premises: emergency telephone provided |
No |
No
|
No |
Emergency phone not visible upon entry to swimming pool. Additional signage added during inspection. Written in to pool rules signs at entry areas. .2530(a) Emergency phone shall be visible from all areas inside pool enclosure. |
|
23
|
4
|
Equipment room: chlorine or bromine automatic feeders that meet NSF Standard 50 |
No |
No
|
No |
Facility has Chlorking Salt system installed. System capable of 5 lbs/day. Required system for salt 12 lbs/day due to sizing of pool. Salt is not approved as primary chlorination. .2535(6) Provide NSF approved automatic chlorinator installed per manufacturer instructions. Liquid chlorinator verified during inspection. Operator will switch to supplementary salt and primary chlorine through liquid. |