5
|
4
|
Water quality: daily written records of water quality and test kit kept on site |
No |
No
|
No |
Records missing total alkalinity, and cyanuric acid weekly .2535(11) Provide record keeping including daily records of disinfectant residual, pH, drain cover/grate inspections, pool water maintenance, and temperature, if applicable. Provide weekly recordings for cyanuric acid and total alkalinity weekly.
*Permit item |
|
8
|
4
|
Pool maintenance: surface skimmers (with weirs, baskets and covers) or gutters clean, in good repair, and functioning properly, no floating debris |
No |
No
|
No |
Some debris in skimmers. .2518(k) Keep skimmers free of debris so skimmers are capable of operating per manufacturer instruction. Operator cleaned. Corrected. |
|
16
|
4
|
Premises: fence or barrier with self-closing, self-latching gates properly constructed and maintained |
No |
No
|
No |
One door from club house not latching or alarmed at time of inspection. Gates being changed out with crash bars, not closing, latching at time of inspection. Mesh has been removed from bottom of latching mechanism.
.2528(a) Ground level doors shall be self-closing, self-latching or child protected by audible alarm.
.2528(a) Gate latches located at less than 54" shall require the use of key, combination lock or card reader or be located on the inside of the gate at least three inches below the top of the gate with no greater than 1/2" opening within 18" of latch mechanism.
*permit item |
|
17
|
4
|
Premises: decks unobstructed, properly drained, free of trip hazards |
No |
No
|
No |
Deck coping chipping by back skimmer.
.2537(2) Decks shall be kept in good repair.
*permit item |
|
24
|
4
|
Equipment room: approved pump, filter, and flow meter operating properly |
No |
No
|
No |
Flow meter not legible and installed on a vertical. .2518(g) Install flow meter on return line per manufacturer instructions.
.2518(g) Flow meter be capable of measuring 1.5 times the design flow rate.
*Permit item |
|
25
|
2
|
Equipment room: equipment and chemicals kept in a dry, well-ventilated enclosure |
No |
No
|
No |
Items within 3' clearance of piping and equipment. Lighting out in pump room. Pool built prior to 2004. .2533(c) Valves and controls shall be accessible to the pool operator at all times. Maintain 3 ft. clear walking space in pump room.
.2533(b) Provide sufficient lighting in pump room. |