Water quality: disinfectant residual provided by |
No |
No
|
No |
.2535(4) Maintain chlorine at least 1.0 ppm through NSF approved chlorinator. Observed the chlorine at 0.2ppm. CDI- adjusted to 1.5ppm through automatic feeder. |
|
22
|
6
|
Premises: emergency telephone provided |
No |
No
|
No |
.2530(f) Signage with legible letters providing dialing instructions, address of pool and pool telephone number shall be posted at the emergency phone. Pool phone number posted incorrect. CDI- correct number posted. |
|
23
|
4
|
Equipment room: chlorine or bromine automatic feeders that meet NSF Standard 50 |
No |
No
|
No |
.2535(6) Automatic chlorine and bromine, and acid feeder pumps shall be automatically prevented from operating when the circulation pump is not in operation. Observed automatic liquid chlorine feeder not turning off when there is no circulation through the pump. Intent to suspend permit issued. Correct within 30 days. |
|
24
|
4
|
Equipment room: approved pump, filter, and flow meter operating properly |
No |
No
|
No |
.2518(e) Provide a spare basket for pump. Observed no spare pump basket. |