Water quality: pool water pH |
No |
No
|
No |
Observed pH below 6.8.
.2535(1) Maintain pH at 7.2 to 7.8. |
|
5
|
4
|
Water quality: daily written records of water quality and test kit kept on site |
No |
No
|
No |
Observed records not being kept regularly. Oberved no checks for CYA in the last 3 months and only one check for TA.
.2535(11) Provide record keeping including daily records of disinfectant residual, pH, drain cover/grate inspections, pool water maintenance, and temperature, if applicable. Provide weekly recordings for cyanuric acid and total alkalinity weekly. |
|
16
|
4
|
Premises: fence or barrier with self-closing, self-latching gates properly constructed and maintained |
No |
No
|
No |
Observed gate not latching. Observed gaps in fence greater than 1/2" within 18" of the unlatch mechagnism.
.2537(b) All gates and doors shall be self-closing, self-latching.
.2528(a) Gate latches located at less than 54" shall require the use of key, combination lock or card reader or be located on the inside of the gate at least three inches below the top of the gate with no greater than 1/2" within 18" of latch mechanism. |
|
23
|
4
|
Equipment room: chlorine or bromine automatic feeders that meet NSF Standard 50 |
No |
No
|
No |
Observed automatic chlorine feeding not turning off when no flow from pump.
.2535(6) Automatic chlorine and bromine feeder pumps shall be automatically prevented from operating when the circulation pump is not in operation. |