Select your filters and click the Search button to search for data, or click Clear to clear all filters
 
Logo Main Menu
Mecklenburg County Health Dept
Public Health Inspections
Select your filters and click the Search button to search for data, or click Clear to clear all filters
 
  
 

Premises Information

Return to Inspections
NameBELL UPTOWN CHARLOTTE
Address355 W MARTIN LUTHER KING JR BLVD
 
City/State/ZIP
CHARLOTTE NC 28202
Premise Type53 - Year-Round Swimming Pool
CountyMecklenburg
Inspection Date 4/6/2017
Final Score @ Grade
32
General Comments16 - General Comment: Windows open on to pool deck. Windows shall not open greater than 4" on to deck. Could not verify during inspection. 22 - General Comment: 911 could clearly hear inspector. Phone breaking in and out. Follow-up with phone and repair so 911 clearly audible.

Violations

 
CDI=Corrected During Inspection  R=Repeat Violation  VR=Verification Required 
Violation Item Demerits Violation Description CDIRVRComments
5 4 Water quality: daily written records of water quality and test kit kept on site No No No No log book and no test kit. Provide test kit. Maintain chlorine, pH, main drain checks daily and acid/alkalinity weekly. Intent to Suspend issued.
8 4 Pool maintenance: surface skimmers (with weirs, baskets and covers) or gutters clean, in good repair, and functioning properly, no floating debris No No No One skimmer basket filled with debris. Keep clean. Corrected during inspection.
15 6 Premises: body hook and ring buoy with throw rope or lifeguard with rescue tube provided and properly located No No No Ring buoy rope not connected to ring buoy. Corrected during inspection.
16 4 Premises: fence or barrier with self-closing, self-latching gates properly constructed and maintained No No No One gate not self-closing - extremely windy day. Will verify on return visit. Inten to Suspend issued.
21 4 Premises: pool and deck lighting provided at pools that operate at night No No No Pool operates at night. Could not verify lighting in pool. Will verify on return visit. Intent to Suspend issued.
24 4 Equipment room: approved pump, filter, and flow meter operating properly No No No Flow meter stuck. Keep operational. Pump leaking. Repair leak.
25 2 Equipment room: equipment and chemicals kept in a dry, well-ventilated enclosure No No No Pump room floor wet due to leak. Keep dry.
29 2 Dressing and sanitary facilities: required fixtures provided, clean, and in good repair No No No Water in restrooms >112 F. Maintain at 110 F or below. Sink stopper damaged in women's restroom. Sink was not draining. Corrected during inspection.
30 2 Dressing and sanitary facilities: approved water source, no cross connections No No No Hose bib in pump room without backflow prevention device. Provide backflow prevention device on all hose bibs.