Water quality: disinfectant residual provided by |
No |
No
|
No |
.2535(4) Maintain chlorine at least 1.0 ppm through NSF approved chlorinator. Observed chlorine at 0.4ppm. CDI- adjusted to 1.5 ppm through chlorinator. |
|
3
|
6
|
Water quality: pool water pH |
No |
No
|
No |
.2535(1) Maintain pH at 7.2 to 7.8. Observed the pH at 7.0. CDI- adjusted to 7.2. |
|
23
|
4
|
Equipment room: chlorine or bromine automatic feeders that meet NSF Standard 50 |
No |
No
|
No |
.2535(6) Automatic chlorine and bromine, and acid feeder pumps shall be automatically prevented from operating when the circulation pump is not in operation. Observed automatic chlorine feeder not turning off when filter pump has no circulation. Correct within 30 days. Intent to suspend permit issued. |
|
24
|
4
|
Equipment room: approved pump, filter, and flow meter operating properly |
No |
No
|
No |
.2518(g) Keep the flow meter operational. Observed flow meter non-operational. Intent to suspend issued. Correct within 30 days. |