Water quality: pool water pH |
No |
No
|
No |
Pool pH at approx. 6.6 - level below what test kit can measure. Operator added chemicals; however, no budge on pH after chemicals added. CYA in pool >100 ppm (at least 140 ppm). Maintain pool pH at 7.2 to 7.8. Lower CYA to ensure pH maintained. Immediate suspension issued. |
|
5
|
4
|
Water quality: daily written records of water quality and test kit kept on site |
No |
No
|
No |
CYA >100 ppm (at least 140 ppm). Lower CYA. Upper limit is 100 ppm.
Some reagents expired. Replace expired reagents.
Total alkalinity and CyA not recorded. Record weekly. |
|
11
|
2
|
Pool maintenance: diving equipment, ladders, steps and handrails properly placed, in good repair |
No |
No
|
No |
Step handrail loose. Tighten. |
|
23
|
4
|
Equipment room: chlorine or bromine automatic feeders that meet NSF Standard 50 |
No |
No
|
No |
No flow meter on chlorinator inlet line. Install per NSF requirement if ever replaced. |
|
24
|
4
|
Equipment room: approved pump, filter, and flow meter operating properly |
No |
No
|
No |
Pump running at 80 gpm. Permit restriction - Pump required at 71 gpm to 74 gpm to meet turnover and flow restriction of the filter. Pump turned down during the inspection. |
|
25
|
2
|
Equipment room: equipment and chemicals kept in a dry, well-ventilated enclosure |
No |
No
|
No |
Pump room floor wet. Could not identify equipment leaking. Ensure pump room floor kept dry.
Bridge over equipment to provide "clearance" moved into chemical storage room. Ensure 3 ft. clearance around equipment.
Chlorine tabs stored in pump room. Moved to chemical storage room during the inspection. Additional chemicals stored in janitor closet on lower level. Ventilation and lighting operable. Ventilation corroded. Does not appear to be chemical resistant and is not "approved" chemical storage room. Store all chemicals in approved chemical storage room. |
|
29
|
2
|
Dressing and sanitary facilities: required fixtures provided, clean, and in good repair |
No |
No
|
No |
One sink not operable in both men's and women's restrooms. One soap dispenser torn off wall in women's restroom. Keep fixtures operable and in good repair. |