Select your filters and click the Search button to search for data, or click Clear to clear all filters
 
Logo Main Menu
Mecklenburg County Health Dept
Public Health Inspections
Select your filters and click the Search button to search for data, or click Clear to clear all filters
 
  
 

Premises Information

Return to Inspections
NameASCHER NORTH, THE
Address640 N CHURCH ST
 
City/State/ZIP
CHARLOTTE NC 28202
Premise Type53 - Year-Round Swimming Pool
CountyMecklenburg
Inspection Date 10/6/2026
Final Score @ Grade
24
General CommentsBrandon Wilson present during the inspection. Pool Closed posted on doors during the inspection. Note: Heater not on at time of inspection. Immediate Suspension issued for: .2535 - maintain pool pH at 7.2 to 7.8 and lower CYA to ensure pH levels maintained.

Violations

 
CDI=Corrected During Inspection  R=Repeat Violation  VR=Verification Required 
Violation Item Demerits Violation Description CDIRVRComments
3 6 Water quality: pool water pH No No No Pool pH at approx. 6.6 - level below what test kit can measure. Operator added chemicals; however, no budge on pH after chemicals added. CYA in pool >100 ppm (at least 140 ppm). Maintain pool pH at 7.2 to 7.8. Lower CYA to ensure pH maintained. Immediate suspension issued.
5 4 Water quality: daily written records of water quality and test kit kept on site No No No CYA >100 ppm (at least 140 ppm). Lower CYA. Upper limit is 100 ppm. Some reagents expired. Replace expired reagents. Total alkalinity and CyA not recorded. Record weekly.
11 2 Pool maintenance: diving equipment, ladders, steps and handrails properly placed, in good repair No No No Step handrail loose. Tighten.
23 4 Equipment room: chlorine or bromine automatic feeders that meet NSF Standard 50 No No No No flow meter on chlorinator inlet line. Install per NSF requirement if ever replaced.
24 4 Equipment room: approved pump, filter, and flow meter operating properly No No No Pump running at 80 gpm. Permit restriction - Pump required at 71 gpm to 74 gpm to meet turnover and flow restriction of the filter. Pump turned down during the inspection.
25 2 Equipment room: equipment and chemicals kept in a dry, well-ventilated enclosure No No No Pump room floor wet. Could not identify equipment leaking. Ensure pump room floor kept dry. Bridge over equipment to provide "clearance" moved into chemical storage room. Ensure 3 ft. clearance around equipment. Chlorine tabs stored in pump room. Moved to chemical storage room during the inspection. Additional chemicals stored in janitor closet on lower level. Ventilation and lighting operable. Ventilation corroded. Does not appear to be chemical resistant and is not "approved" chemical storage room. Store all chemicals in approved chemical storage room.
29 2 Dressing and sanitary facilities: required fixtures provided, clean, and in good repair No No No One sink not operable in both men's and women's restrooms. One soap dispenser torn off wall in women's restroom. Keep fixtures operable and in good repair.