| Violation Item
| Demerits
| Violation Description
| CDI | R | VR |
|
|
3
|
6
|
Water quality: pool water pH |
No |
No
|
No |
Pool pH at 6.8. Operator added bicarb twice to the pool without pH moving upwards. Cyanuric acid was >100 ppm - possibly providing an acid lock. Recommend lowering the cyanuric acid to be able to raise the pH. Maintain pH at 7.2 to 7.8. Immediate suspension issued. |
|
5
|
4
|
Water quality: daily written records of water quality and test kit kept on site |
No |
No
|
No |
Rodney Williams, listed CPO, no longer with property. Provide updated CPO information for CPO for property.
Cyanuric acid >100 ppm. Maintain at 100 ppm or less.
No main drain checks. Provide daily main drain checks in log book. Old log books through July had daily record keeping for main drain checks. New log did not have section for it. |
|
7
|
4
|
Pool maintenance: pool walls and floor kept clean, free of debris and in good repair |
No |
No
|
No |
Algae around steps and also in ladder steps. Keep pool free of algae. |
|
8
|
4
|
Pool maintenance: surface skimmers (with weirs, baskets and covers) or gutters clean, in good repair, and functioning properly, no floating debris |
No |
No
|
No |
Right skimmer missing weir. Repeat item. Replace weir.
Plug in skimmer equalizer on right skimmer rusting out. Replace plug by evacuating water from the line prior to re-plugging. Will give until 2025 operating season to correct. Needs to be corrected when drain covers corrected. |
|
11
|
2
|
Pool maintenance: diving equipment, ladders, steps and handrails properly placed, in good repair |
No |
No
|
No |
Handrail loose at left side steps. Tighten handrail. |
|
15
|
6
|
Premises: body hook and ring buoy with throw rope or lifeguard with rescue tube provided and properly located |
No |
No
|
No |
Grab rope around ring buoy and rope starting to degrade. Provide USCG approved ring buoy with 30 ft. rope. Immediate Suspension issued. |
|
17
|
4
|
Premises: decks unobstructed, properly drained, free of trip hazards |
No |
No
|
No |
Pool furniture 5 ft. to deck edge. Maintain 6 ft. clearance around the pool.
Some damage to slip resistant tread on pool deck. Monitor and repair as needed. Decking shall be slip resistant.
Vegetation in deck drain on right side of pool. Eliminate vegetation to eliminate trip hazard. |
|
23
|
4
|
Equipment room: chlorine or bromine automatic feeders that meet NSF Standard 50 |
No |
No
|
No |
No flow meter on chlorinator. Original construction. Install per NSF requirement. Unable to locate flow meter on chlorinator. |
|
24
|
4
|
Equipment room: approved pump, filter, and flow meter operating properly |
No |
No
|
No |
Flow meter not operable. Provide operable flow meter.
No basket for pump. Provide spare pump basket. |
|
25
|
2
|
Equipment room: equipment and chemicals kept in a dry, well-ventilated enclosure |
No |
No
|
No |
Bicarb and muriatic acid stored in room downstairs. Store in chemical storage room.
Drain cover missing off of drain in pump room. Provide drain cover. |
|
29
|
2
|
Dressing and sanitary facilities: required fixtures provided, clean, and in good repair |
No |
No
|
No |
Men's restroom without soap. Provide soap in restroom. |