2
|
6
|
Water quality: disinfectant residual provided by |
No |
No
|
No |
G.S. 130A-2(3) Chlorine bleached out test kit. Imminent Hazard to public. Lower to measurable level. Observed chlorine bleach out EHS test kit. CDI, pool was drained and chlorine levels were corrected during time of inspection to 10ppm chlorine. |
|
3
|
6
|
Water quality: pool water pH |
No |
No
|
No |
.2535(1) Maintain pH at 7.2 to 7.8. Observed pH at 7.0 at start of inspection, corrected during time of inspection to 7.2 |
|
5
|
4
|
Water quality: daily written records of water quality and test kit kept on site |
No |
No
|
No |
.2535(11) Provide record keeping including daily records of disinfectant residual, pH, drain cover/grate inspections, pool water maintenance, and temperature, if applicable. Provide weekly recordings for cyanuric acid and total alkalinity weekly. Observed temperature not being checked on daily log records. EHS advises pool to start checking the temperature of the heated pool. |
|
22
|
6
|
Premises: emergency telephone provided |
No |
No
|
No |
.2530(f) Signage with legible letters providing dialing instructions, address of pool and pool telephone number shall be posted at the emergency phone. Observed incorrect phone number on emergency phone during time of inspection. CDI, phone number that 911 has was posted and EHS verified that the number called back to the emergency phone. |