NameEMBASSY SUITES AYRSLEY
Address1917 AYRSLEY TOWN BLVD
 
City/State/ZIP
CHARLOTTE NC 28273
Premise Type53 - Year-Round Swimming Pool
CountyMecklenburg
Inspection Date 10/15/2024
Final Score @ Grade
16
General CommentsInspection conducted with CPO Lane Anderson. Tested cyanuric acid at 0ppm today. Facility no longer using stabilized chlorine products. Facility switched from using Triclor to Calcium Hypochlorite tablets. Still using Rainbow chlorinator. This is not approved for use with this product. Recommend replacing with a new chlorinator that is NSF approved for use with Calcium Hypochlorite. *NOTE* These two products can create an explosive reaction if mixed. Pool floor and walls missing plaster in places. Recommend replastering/patching damaged areas. Floor drain not observed in pump room. Immediate suspension issued 22) Contact Will Harrison (704) 507-6824 for re-inspection once issues have been corrected.

Violations

 
CDI=Corrected During Inspection  R=Repeat Violation  VR=Verification Required 
Violation Item Demerits Violation Description CDIRVRComments
8 4 Pool maintenance: surface skimmers (with weirs, baskets and covers) or gutters clean, in good repair, and functioning properly, no floating debris No No No Skimmer closest to the pump room with missing weir. .2518(k) Replace missing weirs. - Intent to suspend item. No flow in skimmer closest to the pump room. EQ and line to pump plugged. .2518(k)(3) The flow-through rate through any one skimmer shall be between 20 GPM and the maximum flow the skimmer is certified for under NSF 50. - Intent to suspend item.
11 2 Pool maintenance: diving equipment, ladders, steps and handrails properly placed, in good repair No No No Ladder loose. Ladder missing endcap. .2521 Install ladders per manufacturer instructions. Ladder step missing non-slip tread. .2521(b) Ladders shall have slip-resistant tread.
22 6 Premises: emergency telephone provided No No No Posted emergency phone number goes to front desk. Front desk did not answer when number was called. .2530(f) Emergency phone shall remain operable. - Immediate suspension item. Emergency phone not functioning. .2530(f) Emergency phone shall remain operable. - Immediate suspension item.
24 4 Equipment room: approved pump, filter, and flow meter operating properly No No No Vacuum cap designed to be opened with push tab.2518(f) Provide self-closing vacuum cap designed to be opened with a tool for pools built after May 1, 2010. - Intent to suspend item.