11
|
2
|
Pool maintenance: diving equipment, ladders, steps and handrails properly placed, in good repair |
No |
No
|
No |
.2521 Install ladders per manufacturer instructions.
observed end cap missing on ladder. |
|
22
|
6
|
Premises: emergency telephone provided |
No |
No
|
No |
.2530(f) Signage with legible letters providing dialing instructions, address of pool and pool telephone number shall be posted at the emergency phone. emergency phone sign was incorrect. sign edited by CPO temporarily to reflect correct street address name.
CDI |
|
24
|
4
|
Equipment room: approved pump, filter, and flow meter operating properly |
No |
No
|
No |
.2518(g) Flow meter be capable of measuring 1.5 times the design flow rate.
flow meter only measures to 120GPM. design flow rate is 100PGPM.
CPO will install flow meter that can read up to 150GPM. (C.Sells)
Per CPO flow meter will be replaced today. REHS will verify. |
|
29
|
2
|
Dressing and sanitary facilities: required fixtures provided, clean, and in good repair |
No |
No
|
No |
.2626(k) Provide shatterproof mirrors.
restroom mirrors are not shatterproof |