| Violation Item
| Demerits
| Violation Description
| CDI | R | VR |
|
|
2
|
6
|
Water quality: disinfectant residual provided by |
No |
No
|
No |
0.1 ppm Cl. .2535(4) Maintain chlorine at least 1.0 ppm. - Pre-permit item. |
|
7
|
4
|
Pool maintenance: pool walls and floor kept clean, free of debris and in good repair |
No |
No
|
No |
Pool floor dirty. Some algae growing on the walls. Skimmers not functioning, pollen and other debris on the water surface. .2537(14) Keep pool surface and pool floor free of debris. - Pre-permit item. |
|
8
|
4
|
Pool maintenance: surface skimmers (with weirs, baskets and covers) or gutters clean, in good repair, and functioning properly, no floating debris |
No |
No
|
No |
Skimmers not functioning. .2518(k) The flow-through rate through any one recessed automatic surface skimmer shall be between 20 gallons per minute and the maximum flow the skimmer is certified for under NSF Standard Number 50. - Operator backwashed and was able to get some flow in skimmers. |
|
11
|
2
|
Pool maintenance: diving equipment, ladders, steps and handrails properly placed, in good repair |
No |
No
|
No |
Handrail loose. .2521 maintain handrails per manufacturer instructions. - Corrected.
Ladder missing endcaps. .2521 Install ladders per manufacturer instructions. |
|
16
|
4
|
Premises: fence or barrier with self-closing, self-latching gates properly constructed and maintained |
No |
No
|
No |
Both gates not self-closing and self-latching. One gate damaged and capable of opening inward. .2528(a) Access gates shall swing away from the pool and be self-latching, self-closing. - Pre-permit item. |
|
22
|
6
|
Premises: emergency telephone provided |
No |
No
|
No |
Made 4 attempts, but unable to call back and connect to Kings III box. .2530(f) Provide functional emergency phone capable of receiving calls in the event of a dropped call. - Pre-permit item. |
|
24
|
4
|
Equipment room: approved pump, filter, and flow meter operating properly |
No |
No
|
No |
Flow meter stuck. .2518(g) Keep flow meter operational. - Flow meter started working after backwashing. |
|
25
|
2
|
Equipment room: equipment and chemicals kept in a dry, well-ventilated enclosure |
No |
No
|
No |
Fan for pump room and chemical storage room not functioning. .2533(e) Provide continuous forced ventilation or cross ventilation in pump room.
.2534(3) Provide continuous forced ventilation or cross ventilation in chemical storage room.
Some chemicals stored in the pump room. Chemical storage room being used for general storage. .2534(2) Pools constructed after April 1, 2004 shall provide a separate room for chemical storage meeting Rule.2534. |
|
28
|
2
|
Dressing and sanitary facilities: bathhouse or rest rooms accessible; shower sign posted |
No |
No
|
No |
Restrooms locked. .2526(a) Provide at least one sink and toilet for residents and guests if furthest unit is more than 300 feet from the pool at hotels, motels, condominiums and apartments. |