| Violation Item
| Demerits
| Violation Description
| CDI | R | VR |
|
|
5
|
4
|
Water quality: daily written records of water quality and test kit kept on site |
No |
No
|
No |
Inadequate record keeping. No Main drain, Total Alkalinity, or Cyanuric Acid checks. Check daily Cl, pH, main drains and record daily pool maintenance activities. Record at least weekly Total Alkalinity and Cyanuric Acid. Maintain Cyanuric Acid at no more than 100ppm. - Intent to suspend item. |
|
6
|
6
|
Submerged suction outlets meet ASME/ANSI A112.19.8-2007. Single drains protected. (.2537, .2539) GPM= ____Field verification complete=____ |
No |
No
|
No |
Pool resurfaced and drain covers changed out in June. Provide updated PDSC. Corrected by operator. |
|
8
|
4
|
Pool maintenance: surface skimmers (with weirs, baskets and covers) or gutters clean, in good repair, and functioning properly, no floating debris |
No |
No
|
No |
One of the chairs on the sunshelf blocking the skimmer. Provide functional skimmers. Corrected by operator. |
|
9
|
4
|
Pool maintenance: depth markings and no diving markers or signs visible and properly located |
No |
No
|
No |
Depth markers on sunshelfs denoted in inches. Depth markers on pool wall and pool deck shall be in at least 4 inch
lettering or 6x6 inch tile. Depth markings shall indicate the depth of the pool in feet of water and shall include the word
"feet" or symbol "ft" to indicate the unit of measurement. Depth markers shall be spaced no more than 25 feet apart when measured
along the perimeter of the pool. If tiles are installed on the deck they shall be slip resistant. - Intent to suspend item. |
|
11
|
2
|
Pool maintenance: diving equipment, ladders, steps and handrails properly placed, in good repair |
No |
No
|
No |
Ladder missing endcaps. Maintain secure and in good condition. |
|
15
|
6
|
Premises: body hook and ring buoy with throw rope or lifeguard with rescue tube provided and properly located |
No |
No
|
No |
Ring buoy missing. Corrected by operator. |
|
16
|
4
|
Premises: fence or barrier with self-closing, self-latching gates properly constructed and maintained |
No |
No
|
No |
Both gates with springs sticking out creating a foothold. Move up to at least 45", or install piece of angled metal above the springs removing the foothold. - Intent to suspend item.
Fence at gate by street with foothold < 45". Remove foot hold by installing angled piece of metal or provide fencing at least 48" high adjacent to the foothold. - Intent to suspend item.
Door from clubhouse not self-latching. Ensure door is either self-closing and self-latching or self-latching and alarmed. - Intent to suspend item. |
|
24
|
4
|
Equipment room: approved pump, filter, and flow meter operating properly |
No |
No
|
No |
Flow meter stuck. Repair or replace. - Intent to suspend item.
Provide spare pump basket for pool pump. - Intent to suspend item. |
|
25
|
2
|
Equipment room: equipment and chemicals kept in a dry, well-ventilated enclosure |
No |
No
|
No |
Most of the floor in the pump room with standing water. Recommend adding additional cuts in the floor to the backwash to drain water.
Fan for pump room and chemical storage room not working. Provide either cross or continuous forced air ventilation. |
|
29
|
2
|
Dressing and sanitary facilities: required fixtures provided, clean, and in good repair |
No |
No
|
No |
No soap in the restrooms. One restroom does not have a working faucet. Maintain restrooms in good working order. |