2
|
6
|
Water quality: disinfectant residual provided by |
No |
No
|
No |
.2535(4) Maintain chlorine at least 1.0 ppm through NSF approved chlorinator. Observed the chlorine at 0.2ppm. Permit suspended. |
|
3
|
6
|
Water quality: pool water pH |
No |
No
|
No |
.2535(1) Maintain pH at 7.2 to 7.8. Observed the pH at 6.8. Permit suspended. |
|
11
|
2
|
Pool maintenance: diving equipment, ladders, steps and handrails properly placed, in good repair |
No |
No
|
No |
Observed one ladder missing rubber end cap in pool. Repair/replace. |
|
12
|
4
|
Pool maintenance: inlets and other fittings in place and in good repair |
No |
No
|
No |
.2537(8) Fittings and/or face plates shall be replaced when damaged and kept in good repair. Observed 2 missing return fittings at deep end of pool. Replace. |
|
16
|
4
|
Premises: fence or barrier with self-closing, self-latching gates properly constructed and maintained |
No |
No
|
No |
.2537(b) All gates and doors shall be self-closing, self-latching. Observed door leading from conference area to pool deck not self-closing or self-latching. This door also has a locking deadbolt that can be rotated by hand on the inside of the building. EHS is requesting this be replaced with a keyed deadbolt so it is not easily accessible. The alternative would be to ensure the door is self-closing and self-latching. |
|
24
|
4
|
Equipment room: approved pump, filter, and flow meter operating properly |
No |
No
|
No |
.2518(e) Provide a spare basket for pump. Observed no spare pump basket. |
|
27
|
2
|
Equipment room: filter backwash discharged through an air gap |
No |
No
|
No |
.2513(b) Filter backwash shall be discharged through an air gap. Observed only an air break, no air gap present. |