11
|
2
|
Pool maintenance: diving equipment, ladders, steps and handrails properly placed, in good repair |
No |
No
|
No |
.2521 Install ladders per manufacturer instructions. Observed ladder to be loose and need to be repaired. Correct the ladder. |
|
12
|
4
|
Pool maintenance: inlets and other fittings in place and in good repair |
No |
No
|
No |
.2537(8) Fittings and/or face plates shall be replaced when damaged and kept in good repair. Observed underwater light fitting to be unsecured. Observed vacuum line fitting to be missing with the suction off. The vacuum line cover needs to be replaced. 30 day I.T.S. Issued. Deadline for correction is 4/17/2026. Failure to correct the issue may result in closure of the pool. |
|
16
|
4
|
Premises: fence or barrier with self-closing, self-latching gates properly constructed and maintained |
No |
No
|
No |
.2528(a) Ground level doors shall be self-closing, self-latching or child protected by audible alarm. Observed door to the pool deck that is usually kept locked and alarmed to be unlocked with the alarm not working. Door was locked and the alarm will be reactivated. -CDI.
Observed fence to be not built to current specifications. Pool built in 1972. |
|
27
|
2
|
Equipment room: filter backwash discharged through an air gap |
No |
No
|
No |
.2513(b) Filter backwash shall be discharged through an air gap. Observed no air gap for the backwash line. |