Select your filters and click the Search button to search for data, or click Clear to clear all filters
 
Logo Main Menu
Mecklenburg County Health Dept
Public Health Inspections
Select your filters and click the Search button to search for data, or click Clear to clear all filters
 
  
 

Premises Information

Return to Inspections
NameCENTRAL POINTE
Address4933 CENTRAL AVENUE
 
City/State/ZIP
CHARLOTTE NC 28205
Premise Type53 - Year-Round Swimming Pool
CountyMecklenburg
Inspection Date 6/2/2016
Final Score @ Grade
32
General CommentsLobby door must be kept locked at all times or be provided with an alarm upon opening.

Violations

 
CDI=Corrected During Inspection  R=Repeat Violation  VR=Verification Required 
Violation Item Demerits Violation Description CDIRVRComments
3 6 Water quality: pool water pH No No No Observed pH to be 6.8 or lower. pH must be 7.2-7.8.
8 4 Pool maintenance: surface skimmers (with weirs, baskets and covers) or gutters clean, in good repair, and functioning properly, no floating debris No No No Observed 2 skimmers out of 3 missing weirs. Replace the weirs.
15 6 Premises: body hook and ring buoy with throw rope or lifeguard with rescue tube provided and properly located No No No Observed rope on buoy to be 46ft. 50ft. rope length is required.
21 4 Premises: pool and deck lighting provided at pools that operate at night No No No Observed pool light housing to be missing entirely. This presents a physical hazard.
23 4 Equipment room: chlorine or bromine automatic feeders that meet NSF Standard 50 No No No Observed salt system to be flashing "LO SALT" and back-up cl2 feeder disconnected. Observed cl2 tablets in skimmer baskets. This is not allowed as this situation presents a hazard.
24 4 Equipment room: approved pump, filter, and flow meter operating properly No No No Observed pump and filter to be turned off at the time of arrival. Pump system must work properly.
27 2 Equipment room: filter backwash discharged through an air gap No No No Observed no backwash line air gap.
33 2 Dressing and sanitary facilities: hose bibbs and floor drains provided No No No Observed hose bibb in need of backflow preventer.