Select your filters and click the Search button to search for data, or click Clear to clear all filters
 
Logo Main Menu
Mecklenburg County Health Dept
Public Health Inspections
Select your filters and click the Search button to search for data, or click Clear to clear all filters
 
  
 

Premises Information

Return to Inspections
NameAVA SOUTHEND
Address335 DOGGETT STREET
 
City/State/ZIP
CHARLOTTE NC 28203
Premise Type53 - Year-Round Swimming Pool
CountyMecklenburg
Inspection Date 7/19/2022
Final Score @ Grade
20
General CommentsInspection completed with Lucas Wyszumiala present. Immediate suspension issued for low chlorine. Contact the front office at 980.314.1620 to lift the suspension once the chlorine is corrected. Ensure gate leading onto pool deck is self-closing or an intent to suspend the permit may be issued.

Violations

 
CDI=Corrected During Inspection  R=Repeat Violation  VR=Verification Required 
Violation Item Demerits Violation Description CDIRVRComments
2 6 Water quality: disinfectant residual provided by No No No .2535(4) Maintain chlorine at least 1.0 ppm. Observed chlorine at 0.3 ppm. Immediate suspension issued. Contact 980.314.1620 to reopen pool once chlorine is adjusted to at least 1.0ppm.
8 4 Pool maintenance: surface skimmers (with weirs, baskets and covers) or gutters clean, in good repair, and functioning properly, no floating debris No No No .2518(k) Water level shall be maintained above the level of the overflow trough on gutter. Observed water level low. CDI- pool filled with additional water.
16 4 Premises: fence or barrier with self-closing, self-latching gates properly constructed and maintained No No No .2537(b) All gates and doors shall be self-closing, self-latching. Observed 1 gate not self-latching. Correct or an intent to suspend may be issued.
24 4 Equipment room: approved pump, filter, and flow meter operating properly No No No .2518(g) Keep flow meter operational. Observed stuck flow meter.
25 2 Equipment room: equipment and chemicals kept in a dry, well-ventilated enclosure No No No .2533(d) Pump room floor shall be kept dry and free of standing water. Observed water accumulating on pump room floor due to leaking pipe.