Water quality: daily written records of water quality and test kit kept on site |
No |
No
|
No |
No log book and test kit. Record chlorine, pH and main drain checks daily. Cyanuric acid and alkalinity weekly. Intent to Suspend issued. |
|
7
|
4
|
Pool maintenance: pool walls and floor kept clean, free of debris and in good repair |
No |
No
|
No |
Severe etching in pool floor and walls. Keep in good repair. |
|
9
|
4
|
Pool maintenance: depth markings and no diving markers or signs visible and properly located |
No |
No
|
No |
One No Diving marker loose. Secure to pool deck. Intent to Suspend issue. |
|
16
|
4
|
Premises: fence or barrier with self-closing, self-latching gates properly constructed and maintained |
No |
No
|
No |
>1/2" within 18" of pushbar. Plexiglas was installed previously and has since broken off. Provide meshing, solid piece so provides no greater than 1/2" within 18" of the latch mechanism.
44" between horizontals on fencing without mesh. Maintain at least 45" between horizontals. Repair with meshing or solid piece.
Electrical boxes on outside of fence provide foothold. Lower than 45". Provide angle over electrical GFCI to eliminate foothold.
Intent to Suspend issued for all listed items. |
|
21
|
4
|
Premises: pool and deck lighting provided at pools that operate at night |
No |
No
|
No |
Pool hours indicate 9:00 am to 10:00 pm. Lighting provided in pool and on deck but not adequate lighting. Provide at least 10 ft cancles of light or limit hours to dawn to dusk. Intent to Suspend issued. |
|
24
|
4
|
Equipment room: approved pump, filter, and flow meter operating properly |
No |
No
|
No |
New chlorination system installed. Automated system. Verified in field and does not turn off when pump turns off. Repair so that chlorination system turns off when pump turns off. Intent to Suspend issued. |