7
|
1
|
Facilities provided, accessible, clean, good repair |
No |
No
|
No |
REPEAT:
.1312 (a) All institutions shall provide toilet, handwashing, and bathing facilities that are available for use by residents and staff. These facilities shall be kept clean and in good repair.- Observed slow draining at hand sink in the room 704, 508, 608, 305, 209, women restroom front hallway, need repair. Observed disrepair faucet in 808 needs repair. Ensure to keep hall hand sinks in good repair. Keep all handwashing sinks in good repair. Point remain the same. |
|
8
|
0
|
Toilet rooms free of storage, handwash signs posted |
No |
No
|
No |
General Comment:
.1312 (b) Bathrooms shall not be used for storage of items not currently in use.- Observed walkers stored in the spa on 100/200 hall. Ensure to only store bathroom related items in the spa at anytime. |
|
10
|
0
|
Handwashing facilities properly located and equipped |
No |
No
|
No |
General Comment:
.1312 (d) Handwashing facilities shall be supplied with soap and disposable towels or hand-drying devices.- Observed no paper towels at hand sink in clean/ soiled utility room 300/400 service hall, room 402, 700/800 service hall soiled utility room. Ensure to supply all handwashing sinks washing supplies at all hand sinks at all times. |
|
16
|
3
|
Hot water between 105°F and 116°F |
No |
No
|
No |
REPEAT
.1313 (d) Institutions shall provide water heating facilities. Hot and cold running water under pressure shall be provided to carry out all operations. Hot water shall be provided at temperatures between 105 degrees Fahrenheit and 116 degrees Fahrenheit at handwashing and bathing facilities. Observed hot water temperature measured more than 120F on half of the building (100/200 & 300/400 hall), and the other half of the building measured in their 90F (500/600 & 700/800 hall). At the salon sink measured 128F, Room 202, 209, 108, 402, 407, 305, 309, spa measured between 122F- 128F. Rehab room measured at 137F. Room 503, 508, 604, 608, 704, 709, 808 measured between 89F- 99F.
NOTE: The facility shall provide tempered water range between 105- 116F at anytime. |